2021-01-19 15:10:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) NEED TO SHOW LOCATION OF DISCONNECT REQUIRED BY |
| SECTION 600.6(B) |
| |
| 600. 6 DISCONNECTS (A) LOCATION. |
| (1) AT POINT OF ENTRY TO A SIGN ENCLOSURE. THE |
| DISCONNECT |
| SHALL BE LOCATED AT THE POINT THE FEEDER CIRCUIT OR |
| BRANCH CIRCUIT(S) |
| SUPPLYING A SIGN OR OUTLINE LIGHTING SYSTEM ENTERS A |
| SIGN ENCLOSURE |
| OR A POLE IN ACCORDANCE WITH 600.5(C)(3) AND SHALL |
| DISCONNECT |
| ALL WIRING WHERE IT ENTERS THE ENCLOSURE OF THE SIGN OR |
| POLE. |
| |
| 2) VALUE FOR THIS INSTALLATION IS TOO LOW, PLEASE |
| SUBMIT A SIGNED CONTRACT WITH THE OWNER. |
| |
| 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| |