Plan Review Notes
Plan Review Notes For Permit 20110374
Permit Number 20110374
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-19 14:57:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SOUND TESTS FOR THE LVT WAS DONE WITH A
 SUSPENDED CEILING AND DOES NOT MATCH THE FIELD
 CONDITIONS FOR THIS PROJECT. FBC 107.1.2
  
 2) THE REQUIRED FLAME SPREAD TEST WAS NOT SUBMITTED.
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
  
 3) FOR SOME REASON THE SAME DOCUMENTS WERE UPLOADED
 MULTIPLE TIMES. YOU ONLY NEED TO UPLOAD ONE COPY OF
 EACH DOCUMENT.
  
  