2020-12-07 16:56:03 | PLAN REVIEW / ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2014 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE LUMINAIRE AND OUTLET IN ATTIC FOR A/H. |
| E3901.12 HVAC OUTLET. M1305.3.1. |
| |
| 2. PROVIDE GFCI OUTLET AT 2ND FLOOR BALCONY. |
| E3901.7 OUTDOOR OUTLETS. |
| |
| 3. PROVIDE 2ND GROUND ROD AT SERVICE. |
| RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A |
| SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL |
| GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN |
| ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| NEC 250.53(A)(2); FBC RE E3608.4 |
| |
| 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. |
| LUMINAIRES: ENERGY CODE ? FBC EC C405.1, R404.1 |
| A NOTE ON PLANS WILL SUFFICE. |
| |
| 5. PROVIDE COMPLIANCE: A NOTICE IS POSTED ON THE |
| ELECTRIC SERVICE PANEL INDICATING TO THE HOMEOWNER THAT |
| THE AIR HANDLER IS LOCATED IN THE ATTIC. SAID NOTICE |
| SHALL BE IN ALL CAPITALS, IN 16-POINT TYPE, WITH THE |
| TITLE AND FIRST PARAGRAPH IN BOLD: |
| SECTION R405. |
| A NOTE ON PLANS WILL SUFFICE. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |
| |
| |
| |