2020-11-23 14:43:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20110345 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE LENGTH OF PIPE FROM WHERE YOU |
| WILL ADD REGULATOR ON MAIN LINE TO THE 1 INCH CSST. FBC |
| FG 402.4.1 |
| |
| 2) PLEASE PROVIDE PRESSURE OF REGULATOR YOU WILL ADD TO |
| THE MAIN LINE. FBC FG 410.1 |
| |
| 3) LONGEST RUN IS NOT 35 FEET, TO FIND THE LONGEST |
| DEVELOPED LENGTH FOR GAS LINE SIZING YOU AND EACH |
| BRANCH FROM THE GAS METER TO THE MOST REMOTE APPLIANCE. |
| PLEASE PROVIDE THE LONGEST DEVELOPED LENGTH DISTANCE |
| FROM THE METER TO THE MOST REMOTE APPLIANCE. THE |
| ORIGINAL PLAN (06060500) FOR THE GAS SYSTEM CALCULATES |
| OUT TO BE 92 FEET FOR THE LONGEST DEVELOPED LENGTH. |
| THAT SYSTEM WAS SIZED FOR THE MAX. BTU OF 195 BTU?S FBC |
| FG 402.4.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |