Plan Review Notes
Plan Review Notes For Permit 20110342
Permit Number 20110342
Review Stop B
Sequence Number 4
Notes
Date Text
2021-03-05 08:29:12NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) STORAGE ROOM NEXT TO THE GARAGE SHOWS FLOOD VENTS -
 THE EXTERIOR GRADE APPEARS HIGH - PLEASE SHOW THE
 EXTERIOR GRADE TO COMPLY WITH FBC
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT: THE BOTTOM OF EACH OPENING SHALL
 BE NOT MORE THAN 1 FOOT (305 MM) ABOVE THE HIGHER OF
 THE FINAL INTERIOR GRADE OR FLOOR AND THE FINISHED
 EXTERIOR GRADE IMMEDIATELY UNDER EACH OPENING.
 2) THE STORAGE ROOM WALLS AND FLOORING BELOW BASE FLOOD
 ELEVATION NEED TO COMPLY WITH FBC R322.1.8
 FLOOD-RESISTANT MATERIALS.
 BUILDING MATERIALS AND INSTALLATION METHODS USED FOR
 FLOORING AND INTERIOR AND EXTERIOR WALLS AND WALL
 COVERINGS BELOW THE ELEVATION REQUIRED IN SECTION
 R322.2 OR R322.3 SHALL BE FLOOD DAMAGE-RESISTANT
 MATERIALS THAT CONFORM TO THE PROVISIONS OF FEMA TB-2.
 3) DRAWING C-1 HAS NOT BEEN REVISED - DRAWING "C1"
 SHOWS THE FFE AT 7.63 NAVD - PLEASE REVISE AS THE FLOOR
 PLANS WERE REVISED TO SHOW 8.13 NAVD
 4) DRAWING C-1 - PLEASE SHOW ELEVATIONS USING NAVD -
 LEGEND ON DRAWING C-1 SHOWS ELEVATIONS USING NGVD BUT
 THE FLOOR ELEVATION IS SHOWN USING NAVD.
 ELEVATION CERTIFICATE =
 A8 PLEASE SHOW THE SQUARE FOOTAGE FOR THE STORAGE ROOM
 (ENCLOSED FLOOR).
 C2(A) PLEASE SHOW THE TOP OF ENCLOSURE FLOOR ELEVATION.
 C2(B) PLEASE SHOW THE TOP OF THE NEXT HIGHEST FLOOR
 (THE FIRST FLOOR OF THE HOUSE)
 C2(F) THE LOWEST ADJACENT GRADE IS ABOVE THE STORAGE
 ROOM AND GARAGE FLOOD VENTS?
  
 5) ROOFING SYSTEM TO BE DEFERRED.
  
  
  