Date |
Text |
2021-01-13 15:24:41 | NEW SFR |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) FLOOD ZONE IS SHOWN ON DRAWING A-003 AS AE 6 - THE |
| BUILDING "LOWEST FLOOR" (FBC R322.1.5) WILL NEED TO BE |
| 8.00 NAVD PER CITY ORDINANCE 4729-17 SEC. 18-33 (1). |
| BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT |
| DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST |
| FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION |
| PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER |
| IS HIGHER. |
| 2) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE FOR |
| BUILDINGS IN FLOOD ZONES (AE6) |
| 3) PLEASE SHOW EQUIPMENT PAD ELEVATIONS TO MEET |
| REQUIREMENTS FBC R322.1.6 |
| 4) ADDING FLOOD VENTS TO A GARAGE OVERHEAD DOOR WILL |
| VOID THE MIAMI DADE NOA FOR THE OVERHEAD DOOR. PLEASE |
| PROVIDE A FIX. |
| 5) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS. |
| 6) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA |
| STATE ROOFING PRODUCT APPROVALS. |
| 7) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE DESIGNER OF RECORD OR LISTED ON THE |
| DRAWINGS.(PLEASE CHECK THE LISTED PRODUCT APPROVAL |
| NUMBERS ON THE DRAWINGS - I CANNOT FIND SOME OF THEM ON |
| THE FLORIDA STATE PRODUCT APPROVAL WEB SITE). |
| 8) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT APPROVALS |
| MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE |
| DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1 |
| DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| BUILDING OFFICIAL. |
| 9) A GUARD RAIL IS REQUIRED FOR THE 2ND FLOOR GUEST |
| ROOM EXTERIOR DOOR FBC R312 |
| |
| |