2020-11-30 16:06:451ST REVIEW FBC-2017 RES.
 PERMIT- 20110342
 11/30/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE SEPARATE PERMITS ARE REQUIRED FOR THE
 GAS PIPING, WATER SERVICE BACKFLOW PREVENTER, POOL, AND
 IRRIGATION SYSTEM- SECTIONS 105.1 & 107.2.1 WPB.
 COMPLETE PLANS AND SPECIFICATIONS ARE REQUIRED.
  
 A) THE GAS PIPING LAYOUT AND RISER DRAWING SHOWN ON THE
 PLANS WERE NOT REVIEWED AT THIS TIME. PLEASE SUBMIT THE
 DRAWINGS UNDER A SEPARATE PERMIT AND INCLUDE
 MANUFACTURER'S SPECIFICATIONS FOR ALL GAS APPLIANCES
 AND EQUIPMENT.
  
 B) BACKFLOW PREVENTER: A FLORIDA LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE WPB BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 2) THE ENERGY FORM R405-2017 INDICATES THE TANKLESS
 WATER HEATER TO BE 50 GALLONS AND 0.97 EFFICIENCY.
 CORRECT THE GALLON SIZE DATA AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS TO CONFIRM THE EFFICIENCY RATING- TABLE
 C404.1 FBC- EC.
  
 3) SHEET PS.1.1: THE LOCATION OF THE 2-WAY CLEANOUT
 SHALL BE AT THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER OR WITHIN 10 FT. UPSTREAM OF THE
 JUNCTION. PLEASE NOTE THAT BUILDING DRAIN BY DEFINITION
 EXTENDS 30 INCHES BEYOND THE EXTERIOR WALL AT WHICH
 POINT IT TRANSITIONS INTO THE BUILDING SEWER- SECTIONS
 R202 & P3005.2.3 FBC RES.
  
 4) SHEET P0.3 & P1.0B: CLEANOUTS AND ACCESS TO THE
 CLEANOUTS ARE REQUIRED WHERE THE VERTICAL RAIN WATER
 LEADERS CONNECT WITH THE HORIZONTAL UNDERSLAB STORM
 DRAINS- SEE SECTIONS 1101.8, 708.1.4, 708.1.10 FBC P
 AND P3005.2.4, AND P3005.2.10 FBC RES.
  
 5) P1.1A: PROVIDE WATER HAMMER ARRESTORS FOR SUPPLY
 LINES TO THE DISHWASHER, ICE MAKER, AND WASHING
 MACHINE- SECTION P2903.5 FBC RES.
  
 6) P1.1A: PROVIDE A BACKFLOW PREVENTER FOR THE SUPPLY
 LINE TO THE ICE MAKER- SECTION P2902.1 FBC RES.
  
 7) P1.1A: INDICATE HOW THE SUPPLY LINES UNDER THE SLAB
 WILL BE PROTECTED FROM CORROSION- SECTION P2603.3 FBC
 RES.
  
 8) A1-101.2 & A-102: PROVIDE THE DIMENSIONS OF THE
 SHOWERS- SECTION P2708.1 FBC RES.
  
 9) P0.2: PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1
 & P2709.2 FBC RES.
  
 10) P1.3: PLEASE NOTE UPON COMPLETION OF THE NEW STORM
 DRAINAGE SYSTEMS AS SHOWN ON THE PLAN A CERTIFICATION
 FROM A LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE FINAL APPROVAL- SECTION
 110.9 IMPACT OF CONSTRUCTION WPB.
  
 11) P1.3: THE ROOF DRAINAGE SYSTEMS SHALL BE IN
 COMPLIANCE WITH SECTIONS R903.4.1 FBC RES AND 1101.2
 FBC P:
  
 A) VERIFY THE ROOF IS DESIGNED FOR THE MAXIMUM POSSIBLE
 DEPTH OF WATER THAT WILL POND THEREON AS DETERMINED BY
 THE RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS,
 SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION
 WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING
 THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF
 DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED- SECTION
 1101.7 FBC P.
  
 B) PROVIDE THE ROOF DRAIN FLOW RATE BASED ON SECTION
 1105.2, AND CALCULATIONS FOR SIZING THE PRIMARY
 VERTICAL CONDUCTORS AND LEADERS AND HORIZONTAL BRANCHES
 BASED ON SECTIONS 1106.1, FIGURE 1106.1 AND SECTION
 1108.3.
  
 C) PROVIDE A PRIMARY ROOF DRAIN INSTALLATION DETAIL.
 SHOW THE MAKES AND MODELS OF THE PRIMARY ROOF DRAINS,
 AND SUBMIT PRODUCT SPECIFICATION SHEETS- SECTIONS
 1102.6 AND 1108.1.
  
 D) PROVIDE AN OVERFLOW SCUPPER DETAIL PER SECTIONS
 R903.4.1 FBC RES. AND 1108.3 FBC P.
  
 E) SHOW THE LOCATIONS OF GUTTERS FOR THE SLOPED ROOFS
 AND PROVIDE VERTICAL LEADER AND HORIZONTAL GUTTER SIZES
 IN ACCORDANCE WITH TABLES 1106.3 AND 1106.6.
  
 12) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER