2020-11-30 13:37:50 | PLAN REVIEW / PLUMBING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PROVIDE A PLUMBING PLAN. |
| |
| 1. COMPLETE |
| |
| 2. PROVIDE SHOWER PAN DETAIL. |
| |
| P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1 |
| WHERE A SHOWER RECEPTOR HAS A FINISHED CURB THRESHOLD, |
| IT SHALL BE NOT LESS THAN 1 INCH (25 MM) BELOW THE |
| SIDES AND BACK OF THE RECEPTOR. THE CURB SHALL BE NOT |
| LESS THAN 2 INCHES (51 MM) AND NOT MORE THAN 9 INCHES |
| (229 MM) DEEP WHEN MEASURED FROM THE TOP OF THE CURB TO |
| THE TOP OF THE DRAIN. THE FINISHED FLOOR SHALL SLOPE |
| UNIFORMLY TOWARD THE DRAIN NOT LESS THAN 1/4 UNIT |
| VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) NOR |
| MORE THAN 1/2 UNIT VERTICAL PER 12 UNITS HORIZONTAL |
| (4-PERCENT SLOPE) AND FLOOR DRAINS SHALL BE FLANGED TO |
| PROVIDE A WATER-TIGHT JOINT IN THE FLOOR. |
| P2709.3 SHOWER PAN LINING INSTALLATION. |
| LINING MATERIALS SHALL BE SLOPED ONE FOURTH UNIT |
| VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) TO |
| WEEP HOLES IN THE SUBDRAIN BY MEANS OF A SMOOTH, |
| SOLIDLY FORMED SUBBASE, SHALL BE PROPERLY RECESSED AND |
| FASTENED TO APPROVED BACKING SO AS NOT TO OCCUPY THE |
| SPACE REQUIRED FOR THE WALL COVERING, AND SHALL NOT BE |
| NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH |
| (25.4 MM) ABOVE THE FINISHED THRESHOLD. |
| |
| P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND |
| TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH |
| CONTROL VALVES OF THE PRESSURE-BALANCE, |
| THERMOSTATIC-MIXING OR COMBINATION |
| PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A |
| HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME |
| A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET |
| TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN |
| 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| USED FOR COMPLIANCE WITH THIS SECTION. |
| |
| 3. SHOW LOCATION OF HOSE BIBS ON FLOOR PLAN. |
| |
| P2903.10HOSE BIBB. |
| |
| HOSE BIBBS SUBJECT TO FREEZING, INCLUDING THE |
| ?FROSTPROOF? TYPE, SHALL BE EQUIPPED WITH AN ACCESSIBLE |
| STOP-AND-WASTE-TYPE VALVE INSIDE THE BUILDING SO THAT |
| THEY CAN BE CONTROLLED AND DRAINED DURING COLD PERIODS. |
| |
| 4.PROVIDE BACKFLOW PREVENTER. |
| |
| BACKFLOW PREVENTER FOR IRRIGATION AND MAIN SERVICE |
| REQUIRED PER THE CITY OF WEST PALM BEACH ORD #2853-95. |
| A PERMIT REQUIRED BY A LICENSED CONTRACTOR AND MUST BE |
| CERTIFIED BY UTILITIES PRIOR TO FINAL INSPECTION. |
| PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| FOR FURTHER DIRECTIONS. |
| |
| P2902.3BACKFLOW PROTECTION. |
| A MEANS OF PROTECTION AGAINST BACKFLOW SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTIONS P2902.3.1 THROUGH |
| P2902.3.6. BACKFLOW PREVENTION APPLICATIONS SHALL |
| CONFORM TO TABLE P2902.3, EXCEPT AS SPECIFICALLY STATED |
| IN SECTIONS P2902.4 THROUGH P2902.5.5. |
| |
| 5. PROVIDE WATER HAMMER DETAIL. |
| |
| P2903.5WATER HAMMER. |
| |
| THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| HAMMER. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |