2020-11-30 11:28:19 | PLAN REVIEW / MECHANICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1.PROVIDE ENGINEERING FOR INSTALLATION OF THE CONDENSER |
| PAD AND MOUNTING OF THE CONDENSER- SECTIONS |
| M1305.1.4.1, M1307.2 AND M1401.4 FBC RES. |
| |
| M1305.1.4.1 GROUND CLEARANCE. |
| EQUIPMENT AND APPLIANCES SUPPORTED FROM THE GROUND |
| SHALL BE LEVEL AND FIRMLY SUPPORTED ON A CONCRETE SLAB |
| OR OTHER APPROVED MATERIAL EXTENDING NOT LESS THAN 3 |
| INCHES (76 MM) ABOVE THE ADJOINING GROUND. SUCH SUPPORT |
| SHALL BE IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS. APPLIANCES SUSPENDED FROM |
| THE FLOOR SHALL HAVE A CLEARANCE OF NOT LESS THAN 6 |
| INCHES (152 MM) FROM THE GROUND. |
| |
| 2. PROVIDE DETAIL FOR BATHROOM EXHAUST FANS |
| |
| M1507.2RECIRCULATION OF AIR. |
| EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS SHALL NOT |
| BE RECIRCULATED WITHIN A RESIDENCE OR TO ANOTHER |
| DWELLING UNIT AND SHALL BE EXHAUSTED DIRECTLY TO THE |
| OUTDOORS. EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS |
| SHALL NOT DISCHARGE INTO AN ATTIC, CRAWL SPACE OR OTHER |
| AREAS INSIDE THE BUILDING. |
| |
| 3. PROVIDE LOCKING FREON PORTS. |
| |
| M1411.8 LOCKING ACCESS PORT CAPS. |
| REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL |
| BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR |
| SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED |
| ACCESS. |
| |
| 4. PROVIDE KITCHEN RANGE EXHAIUST HOOD SPECIFICATIONS. |
| |
| M1503.3 KITCHEN EXHAUST RATES. |
| WHERE DOMESTIC KITCHEN COOKING APPLIANCES ARE EQUIPPED |
| WITH DUCTED RANGE HOODS OR DOWN-DRAFT EXHAUST SYSTEMS, |
| THE FANS SHALL BE SIZED IN ACCORDANCE WITH SECTION |
| M1507.4. |
| |
| 5. PROVIDE RANGE HOOD EXHAUST DETAIL. |
| |
| M1501.1OUTDOOR DISCHARGE. |
| THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM |
| SHALL BE DISCHARGED TO THE OUTDOORS IN ACCORDANCE WITH |
| SECTION M1506.3. AIR SHALL NOT BE EXHAUSTED INTO AN |
| ATTIC, SOFFIT, RIDGE VENT OR CRAWL SPACE. |
| |
| 6. PROVIDE DETAIL FOR A/C CONDENSATE DISPOSAL. |
| |
| M1411.3 CONDENSATE DISPOSAL. |
| CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE |
| CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE |
| OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM |
| HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT |
| LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO |
| A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A |
| NUISANCE. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |