2020-11-30 11:35:33 | PLAN REVIEW / ELECTRIC |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. AIC: - N/A |
| |
| 2. SMOKE DETECTORS ARE MISSING ON 1ST FLOOR. |
| |
| R314.3 LOCATION. |
| SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 1. 1.IN EACH SLEEPING ROOM. |
| 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE |
| IMMEDIATE VICINITY OF THE BEDROOMS. |
| 3. 3.ON EACH ADDITIONAL STORY OF THE DWELLING, |
| INCLUDING BASEMENTS AND HABITABLE ATTICS AND NOT |
| INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN |
| DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND |
| WITHOUT AN INTERVENING DOOR BETWEEN THE ADJACENT |
| LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL |
| SHALL SUFFICE FOR THE ADJACENT LOWER LEVEL PROVIDED |
| THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW |
| THE UPPER LEVEL. |
| 4. 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 |
| FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF |
| A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS |
| THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED |
| BY SECTION R314.3 |
| |
| 3. PROVIDE CARBON MONOXIDE DETECTORS: |
| |
| R314.5 COMBINATION ALARMS. |
| COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE |
| PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS. |
| |
| R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. |
| |
| FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| FEET OF EACH SLEEPING ROOM. |
| |
| 4. HIGH EFFICACY LAMPS |
| |
| PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". |
| |
| A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 |
| |
| 5. PROVIDE GFCI OUTLET AT REAR OF STRUCTURE. |
| |
| E3901.7 OUTDOOR OUTLETS. |
| NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| |
| 6. RE: RISER DIAGRAHM - PANELS A AND B: |
| |
| E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR. |
| AN EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED IN |
| SECTION E3908 SHALL BE RUN WITH THE SUPPLY CONDUCTORS |
| AND CONNECTED TO THE BUILDING OR STRUCTURE |
| DISCONNECTING MEANS AND TO THE GROUNDING ELECTRODE(S). |
| THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE USED FOR |
| GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES OR FRAMES |
| REQUIRED TO BE GROUNDED OR BONDED. THE EQUIPMENT |
| GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH |
| SECTION E3908.12. ANY INSTALLED GROUNDED CONDUCTOR |
| SHALL NOT BE CONNECTED TO THE EQUIPMENT GROUNDING |
| CONDUCTOR OR TO THE GROUNDING ELECTRODE(S). [250.32(B) |
| AND TABLE 250.122] |
| |
| 1ST MEANS OF DISCONNECT |
| E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR |
| CONNECTION. |
| THE GROUNDING ELECTRODE CONDUCTOR SHALL BE CONNECTED TO |
| THE GROUNDED SERVICE CONDUCTOR AT ANY ACCESSIBLE POINT |
| FROM THE LOAD END OF THE OVERHEAD SERVICE CONDUCTORS, |
| SERVICE DROP, UNDERGROUND SERVICE CONDUCTORS, OR |
| SERVICE LATERAL TO AND INCLUDING THE TERMINAL OR BUS TO |
| WHICH THE GROUNDED SERVICE CONDUCTOR IS CONNECTED AT |
| THE SERVICE DISCONNECTING MEANS. A GROUNDING CONNECTION |
| SHALL NOT BE MADE TO ANY GROUNDED CIRCUIT CONDUCTOR ON |
| THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS, |
| EXCEPT AS PROVIDED IN SECTION E3607.3.2. [250.24(A)(1) |
| AND (A)(5)] NEC 250.24 (A) |
| |
| 7. PROVIDE CIRCUT FOR T/W/H IGNITER CIRCUTS. |
| |
| PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| NEC 220; FBC RE E3602.2 |
| |
| 8. PROVIDE INTERSYSTEM BONDING TERMINAL. |
| |
| PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |