2020-11-30 11:35:33PLAN REVIEW / ELECTRIC
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AIC: - N/A
  
 2. SMOKE DETECTORS ARE MISSING ON 1ST FLOOR.
  
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. 1.IN EACH SLEEPING ROOM.
 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE
 IMMEDIATE VICINITY OF THE BEDROOMS.
 3. 3.ON EACH ADDITIONAL STORY OF THE DWELLING,
 INCLUDING BASEMENTS AND HABITABLE ATTICS AND NOT
 INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN
 DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND
 WITHOUT AN INTERVENING DOOR BETWEEN THE ADJACENT
 LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL
 SHALL SUFFICE FOR THE ADJACENT LOWER LEVEL PROVIDED
 THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW
 THE UPPER LEVEL.
 4. 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3
 FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF
 A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS
 THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED
 BY SECTION R314.3
  
 3. PROVIDE CARBON MONOXIDE DETECTORS:
  
 R314.5 COMBINATION ALARMS.
 COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE
 PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS.
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 4. HIGH EFFICACY LAMPS
  
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS".
  
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 5. PROVIDE GFCI OUTLET AT REAR OF STRUCTURE.
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
  
 6. RE: RISER DIAGRAHM - PANELS A AND B:
  
 E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR.
 AN EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED IN
 SECTION E3908 SHALL BE RUN WITH THE SUPPLY CONDUCTORS
 AND CONNECTED TO THE BUILDING OR STRUCTURE
 DISCONNECTING MEANS AND TO THE GROUNDING ELECTRODE(S).
 THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE USED FOR
 GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES OR FRAMES
 REQUIRED TO BE GROUNDED OR BONDED. THE EQUIPMENT
 GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH
 SECTION E3908.12. ANY INSTALLED GROUNDED CONDUCTOR
 SHALL NOT BE CONNECTED TO THE EQUIPMENT GROUNDING
 CONDUCTOR OR TO THE GROUNDING ELECTRODE(S). [250.32(B)
 AND TABLE 250.122]
  
 1ST MEANS OF DISCONNECT
 E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR
 CONNECTION.
 THE GROUNDING ELECTRODE CONDUCTOR SHALL BE CONNECTED TO
 THE GROUNDED SERVICE CONDUCTOR AT ANY ACCESSIBLE POINT
 FROM THE LOAD END OF THE OVERHEAD SERVICE CONDUCTORS,
 SERVICE DROP, UNDERGROUND SERVICE CONDUCTORS, OR
 SERVICE LATERAL TO AND INCLUDING THE TERMINAL OR BUS TO
 WHICH THE GROUNDED SERVICE CONDUCTOR IS CONNECTED AT
 THE SERVICE DISCONNECTING MEANS. A GROUNDING CONNECTION
 SHALL NOT BE MADE TO ANY GROUNDED CIRCUIT CONDUCTOR ON
 THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS,
 EXCEPT AS PROVIDED IN SECTION E3607.3.2. [250.24(A)(1)
 AND (A)(5)] NEC 250.24 (A)
  
 7. PROVIDE CIRCUT FOR T/W/H IGNITER CIRCUTS.
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2
  
 8. PROVIDE INTERSYSTEM BONDING TERMINAL.
  
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  
  
  