 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1,
 1) PLEASE PROVIDE THE MISSING PRODUCT APPROVAL SHEETS
 AND WINDLOAD PRESSURE CALCULATION SHEETS THAT INDICATE
 THE ANCHOR FASTENING PATTERNS AND ADHHESIVE
 PRODUCT/APPLICATION DIRECTIONS FOR MEETING UPLIFT
 REQUIREMENTS.
 2) PLEASE PROVIDE THE MOISTURE SURVEY FOR THE
 LIGHTWEIGHT CONCREET.
 3) PLEASE PROVIDE A CLARIFICATION OF VALUATION, AS
 THESE BUILDINGS (#3 & 4) ARE PERMITTED AS ONE AND AT
 THE SAME TIME VALUE FOR JOB AT BUILDING #5 (HALF THE
 SIZE OF BUILDING #3 & 4 COMBINED) IS THE SAME.