Plan Review Notes
Plan Review Notes For Permit 20110321
Permit Number 20110321
Review Stop P
Sequence Number 2
Notes
Date Text
2021-01-07 16:47:242ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110321
 1/7/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW.
 NOTES IN CAP LETTERS HAVE BEEN ADDED TO COMMENTS FOR
 CLARIFICATION. THE REQUESTED NARRATIVE WHICH WOULD HELP
 EXPEDITE THE REVIEW WAS NOT PROVIDED BY THE ARCHITECT.
  
 2) FAILED. A.05 & A.07: THE REQUIRED DRINKING FOUNTAINS
 SHALL BE ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2,
 & 602.1- 602.6 FBC ACC. PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS SHOWING COMPLIANCE WITH SECTIONS
 306, 307, AND 602 FBC ACC INCLUDING ELEVATION VIEWS
 SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND
 SPOUT LOCATIONS. INDICATE HOW THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2- PROTRUDING OBJECTS INTO
 THE CIRCULATION PATH. SHEET A.07: THE ELEVATION DRAWING
 DOES NOT SHOW THE HIGH FOUNTAIN DETAILS AND COMPLIANCE
 WITH PROTRUDING OBJECTS. THE ELKAY EZ8SL IN THE
 SCHEDULE ON P0.1 IS A SINGLE DRINKING FOUNTAIN- A HI-LO
 IS REQUIRED PER SECTION- SECTIONS 211.2, & 602.1- 602.6
 FBC ACC.
  
 3) FAILED A.05 & A.07: MISSING ACCESSIBLE BATHROOM AND
 BREAKROOM DETAILS- FBC ACC. INCOMPLETE.
  
 A) FAILED CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. NOT PROVIDED. PLEASE
 NOTE THAT IN NEW CONSTRUCTION TOILET COMPARTMENTS THE
 WATER CLOSETS SHALL BE LOCATED IN THE CORNER DIAGONAL
 TO THE DOOR- SECTION 604.8.1.7 FBC ACC.
  
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2.NOT PROVIDED.
  
 D) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONT OF THE WATER CLOSET- SECTION
 604.7. SHEET A.07: THE DETAIL SHOWS THE CENTERLINES AT
 3 FT. FROM THE WALL, NOT 7-9 IN. FROM THE FRONT OF THE
 WATER CLOSETS.
  
 E) FAILED. CLEAR FOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE BREAKROOM SINK- SECTION 606.2. NOT PROVIDED.
  
 F) FAILED. HEIGHT OF THE BREAKROOM SINK MEASURED FROM
 THE FINISHED FLOOR TO THE RIM OF THE SINK OR COUNTER
 SURFACE WHICHEVER IS HIGHER- SECTION 606.3. NOT
 PROVIDED.
  
 3) FAILED. PROVIDE A SLAB REPAIR DETAIL- SECTION
 107.2.1 WPB. NOT PROVIDED.
  
 4) FAILED. PROVIDE A WALL AND FLOOR FINISH SCHEDULE FOR
 THE BATHROOMS AND AT MOP SINK LOCATIONS IN COMPLIANCE
 WITH SECTION 310.3 FBC P, AND SECTIONS 1210.2.1 &
 1210.2.2 FBC B. SHEET A.05: WALL FINISH AT MOP SINK NOT
 IDENTIFIED.
  
 5) FAILED. PROVIDE A PLUMBING FIXTURE SCHEDULE- WATER
 CLOSETS, LAVATORIES, BREAKROOM SINK, FAUCETS, DRINKING
 FOUNTAINS, AND MOP SINK- SEE CHAPTER 4 FBC P. SHEETS-
 P.01, P,02, P,03, & A.05: THE ELKAY EZ8SL IS A SINGLE
 DRINKING FOUNTAIN- A HI-LO IS REQUIRED PER SECTION-
 SECTIONS 211.2, & 602.1- 602.6 FBC ACC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  