2021-01-07 16:47:24 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT- 20110321 |
| 1/7/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW. |
| NOTES IN CAP LETTERS HAVE BEEN ADDED TO COMMENTS FOR |
| CLARIFICATION. THE REQUESTED NARRATIVE WHICH WOULD HELP |
| EXPEDITE THE REVIEW WAS NOT PROVIDED BY THE ARCHITECT. |
| |
| 2) FAILED. A.05 & A.07: THE REQUIRED DRINKING FOUNTAINS |
| SHALL BE ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, |
| & 602.1- 602.6 FBC ACC. PROVIDE DRINKING FOUNTAIN |
| INSTALLATION DETAILS SHOWING COMPLIANCE WITH SECTIONS |
| 306, 307, AND 602 FBC ACC INCLUDING ELEVATION VIEWS |
| SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND |
| SPOUT LOCATIONS. INDICATE HOW THE FOUNTAINS WILL BE IN |
| COMPLIANCE WITH SECTION 307.2- PROTRUDING OBJECTS INTO |
| THE CIRCULATION PATH. SHEET A.07: THE ELEVATION DRAWING |
| DOES NOT SHOW THE HIGH FOUNTAIN DETAILS AND COMPLIANCE |
| WITH PROTRUDING OBJECTS. THE ELKAY EZ8SL IN THE |
| SCHEDULE ON P0.1 IS A SINGLE DRINKING FOUNTAIN- A HI-LO |
| IS REQUIRED PER SECTION- SECTIONS 211.2, & 602.1- 602.6 |
| FBC ACC. |
| |
| 3) FAILED A.05 & A.07: MISSING ACCESSIBLE BATHROOM AND |
| BREAKROOM DETAILS- FBC ACC. INCOMPLETE. |
| |
| A) FAILED CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR |
| THE WATER CLOSETS- SECTION 604.3. NOT PROVIDED. PLEASE |
| NOTE THAT IN NEW CONSTRUCTION TOILET COMPARTMENTS THE |
| WATER CLOSETS SHALL BE LOCATED IN THE CORNER DIAGONAL |
| TO THE DOOR- SECTION 604.8.1.7 FBC ACC. |
| |
| B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| FOR THE LAVATORIES- SECTION 606.2.NOT PROVIDED. |
| |
| D) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER |
| MEASURED FROM THE FRONT OF THE WATER CLOSET- SECTION |
| 604.7. SHEET A.07: THE DETAIL SHOWS THE CENTERLINES AT |
| 3 FT. FROM THE WALL, NOT 7-9 IN. FROM THE FRONT OF THE |
| WATER CLOSETS. |
| |
| E) FAILED. CLEAR FOR SPACE DIAGRAM AND DIMENSIONS FOR |
| THE BREAKROOM SINK- SECTION 606.2. NOT PROVIDED. |
| |
| F) FAILED. HEIGHT OF THE BREAKROOM SINK MEASURED FROM |
| THE FINISHED FLOOR TO THE RIM OF THE SINK OR COUNTER |
| SURFACE WHICHEVER IS HIGHER- SECTION 606.3. NOT |
| PROVIDED. |
| |
| 3) FAILED. PROVIDE A SLAB REPAIR DETAIL- SECTION |
| 107.2.1 WPB. NOT PROVIDED. |
| |
| 4) FAILED. PROVIDE A WALL AND FLOOR FINISH SCHEDULE FOR |
| THE BATHROOMS AND AT MOP SINK LOCATIONS IN COMPLIANCE |
| WITH SECTION 310.3 FBC P, AND SECTIONS 1210.2.1 & |
| 1210.2.2 FBC B. SHEET A.05: WALL FINISH AT MOP SINK NOT |
| IDENTIFIED. |
| |
| 5) FAILED. PROVIDE A PLUMBING FIXTURE SCHEDULE- WATER |
| CLOSETS, LAVATORIES, BREAKROOM SINK, FAUCETS, DRINKING |
| FOUNTAINS, AND MOP SINK- SEE CHAPTER 4 FBC P. SHEETS- |
| P.01, P,02, P,03, & A.05: THE ELKAY EZ8SL IS A SINGLE |
| DRINKING FOUNTAIN- A HI-LO IS REQUIRED PER SECTION- |
| SECTIONS 211.2, & 602.1- 602.6 FBC ACC |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |