Plan Review Notes
Plan Review Notes For Permit 20110321
Permit Number 20110321
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-09 14:13:541ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110321
 12/9/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A.05 & P.01: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING
 FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR
 BUSINESS OCCUPANCIES. REVISE THE ARCHITECTURAL AND
 PLUMBING PLANS TO SHOW THE LOCATIONS AND PLUMBING
 PIPING FOR THE REQUIRED FIXTURES- SECTION 107.2.1 &
 107.3.5.3 WPB.
  
 2) A.05 & A.07: THE REQUIRED DRINKING FOUNTAINS SHALL
 BE ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, &
 602.1- 602.6 FBC ACC. PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS SHOWING COMPLIANCE WITH SECTIONS
 306, 307, AND 602 FBC ACC INCLUDING ELEVATION VIEWS
 SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND
 SPOUT LOCATIONS. INDICATE HOW THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2- PROTRUDING OBJECTS INTO
 THE CIRCULATION PATH.
  
 3) A.05 & A.07: MISSING ACCESSIBLE BATHROOM AND
 BREAKROOM DETAILS- FBC ACC.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
  
 C) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
  
 D) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION 604.7.
  
 E) CLEAR FOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 BREAKROOM SINK- SECTION 606.2.
  
 F) HEIGHT OF THE BREAKROOM SINK MEASURED FROM THE
 FINISHED FLOOR TO THE RIM OF THE SINK OR COUNTER
 SURFACE WHICHEVER IS HIGHER- SECTION 606.3.
  
 3) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 4) PROVIDE A WALL AND FLOOR FINISH SCHEDULE FOR THE
 BATHROOMS AND AT MOP SINK LOCATIONS IN COMPLIANCE WITH
 SECTION 310.3 FBC P, AND SECTIONS 1210.2.1 & 1210.2.2
 FBC B.
  
 5) P3: PROVIDE A PLUMBING FIXTURE SCHEDULE- WATER
 CLOSETS, LAVATORIES, BREAKROOM SINK, FAUCETS, DRINKING
 FOUNTAINS, AND MOP SINK- SEE CHAPTER 4 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  