Text |
2020-12-09 14:13:54 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20110321 |
| 12/9/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A.05 & P.01: PROVIDE PLUMBING FIXTURE |
| CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING |
| FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR |
| BUSINESS OCCUPANCIES. REVISE THE ARCHITECTURAL AND |
| PLUMBING PLANS TO SHOW THE LOCATIONS AND PLUMBING |
| PIPING FOR THE REQUIRED FIXTURES- SECTION 107.2.1 & |
| 107.3.5.3 WPB. |
| |
| 2) A.05 & A.07: THE REQUIRED DRINKING FOUNTAINS SHALL |
| BE ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & |
| 602.1- 602.6 FBC ACC. PROVIDE DRINKING FOUNTAIN |
| INSTALLATION DETAILS SHOWING COMPLIANCE WITH SECTIONS |
| 306, 307, AND 602 FBC ACC INCLUDING ELEVATION VIEWS |
| SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND |
| SPOUT LOCATIONS. INDICATE HOW THE FOUNTAINS WILL BE IN |
| COMPLIANCE WITH SECTION 307.2- PROTRUDING OBJECTS INTO |
| THE CIRCULATION PATH. |
| |
| 3) A.05 & A.07: MISSING ACCESSIBLE BATHROOM AND |
| BREAKROOM DETAILS- FBC ACC. |
| |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| WATER CLOSET- SECTION 604.3. |
| |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORY- SECTION 606.2. |
| |
| C) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| 306. |
| |
| D) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| FROM THE FRONT OF THE WATER CLOSET- SECTION 604.7. |
| |
| E) CLEAR FOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| BREAKROOM SINK- SECTION 606.2. |
| |
| F) HEIGHT OF THE BREAKROOM SINK MEASURED FROM THE |
| FINISHED FLOOR TO THE RIM OF THE SINK OR COUNTER |
| SURFACE WHICHEVER IS HIGHER- SECTION 606.3. |
| |
| 3) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. |
| |
| 4) PROVIDE A WALL AND FLOOR FINISH SCHEDULE FOR THE |
| BATHROOMS AND AT MOP SINK LOCATIONS IN COMPLIANCE WITH |
| SECTION 310.3 FBC P, AND SECTIONS 1210.2.1 & 1210.2.2 |
| FBC B. |
| |
| 5) P3: PROVIDE A PLUMBING FIXTURE SCHEDULE- WATER |
| CLOSETS, LAVATORIES, BREAKROOM SINK, FAUCETS, DRINKING |
| FOUNTAINS, AND MOP SINK- SEE CHAPTER 4 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |