2020-12-05 08:51:37 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20110321 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE CHECK THE CFM?S OF THE AHU?S, THE AHU?S ARE |
| PROVIDING 2000CFM?S OF AIR FLOW TO EACH AREA. THE |
| MECHANICAL LEGEND INDICATES THAT THE AHU?S MAX AIR FLOW |
| IS 1890 @ .5 INCH. FBC EC C403.2.1 |
| |
| 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. FBC EC 403.2.1 |
| |
| 3) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION BASED ON |
| THE USE OF EACH SPACE. IT APPEARS THAT THERE ARE |
| OFFICES AND SHOWROOMS IN THIS BUILDING. EACH WOULD BE |
| FIGURED DIFFERENTLY BASED ON TABLE 403.3.1.1 FBC M. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |