Plan Review Notes
Plan Review Notes For Permit 20110321
Permit Number 20110321
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-11-18 15:46:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 05 - THE BATHROOM RR - 2 DOOR SWINGS OUT
 INTO THE PATH OF EGRESS AND ENCROACHES ON THE REQUIRED
 EGRESS WITH LEADING TO THE SAMPLE ROOM.
  
 THERE IS AN EXIT SIGN OVER THAT DOOR LEADING INTO THE
 SAMPLE ROOM.
  
 PER NFPA 101, CH 7
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 THE BATHROOM DOOR WIS REQUIRED TO SWING INTO THE
 BATHROOM OF THE EXIT SIGN CAN BE MOVED TO OVER THE
 BREAKROOM DOOR AS LONG AS THE HARDWARE MEETS THE
 REQUIREMENTS OF NFPA 101, CH 7 MEANS OF EGRESS.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  