Plan Review Notes
Plan Review Notes For Permit 20110321
Permit Number 20110321
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-20 15:38:21WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110321
 ADD: 6417 GEORGIA AVE.
 CONT: MASTER CONSTRUCTION
 TEL: 561-248-5498
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 20TH/2020
 ACTION: DENIED
  
 1) SHEET A.05 BUILDING CODE ANALYSIS:
 1A) UNDER THE HEADING OCCUPANCY SEPARATION FBC TABLE
 303.3.2 1HR. STAND ALONE STRUCTURE. PLEASE EXPLAIN WHAT
 IS MEANT, THERE IS NO TABLE 303.3.2 IN THE 2017
 FBC-BUILDING CODE BOOK. FOR STAND ALONE STRUCTURES YOU
 WOULD CONSIDER LOOKING AT TABLE 602 FIRE RESISTANCE
 RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE FROM PROPERTY LINES OR OTHER
 BUILDINGS ON THE SAME LOT.
  
 1B) UNDER THE HEADING CONSTRUCTION TYPE THIS BUILDING
 IS LISTED AS CONSTRUCTION TYPE III-B (TABLE 601) 2 HRS.
 OR LESS.
 PLEASE DEFINE WHICH WALLS REQUIRE THE 2-HOUR FIRE
 RATING AND WITH AN EXISTING BUILDING HOW WILL THE WALL
 RATING BE DETERMINED. TABLE 601 FOOTNOTES E & F NEED TO
 BE REVIEWED. FOOTNOTE F ALSO REFERENCES SECTION 704.10.
 PLEASE ALSO CONSIDER IN THE 2017 FBC-B TABLE
 506.2BUILDING TYPE V-B ALLOWS FOR A BUSINESS OCCUPANCY
 TO BE UP TO 9,000 SQ. FT. AND THAT IS WITHOUT FRONTAGE
 INCREASES. TABLE 602 WOULD ONLY REQUIRE A 1-HOUR FIRE
 RATING BECAUSE OF THE ZERO-LOT LINE ON THE NORTH WALL.
  
 1C) UNDER THE HEADING OF TENANT OCCUPANT LOAD AND
 REFERENCING TABLE 1004.1.2 BUT THE OCCUPANT LOAD IS
 NEVER GIVEN. 2017 FBC-B TABLE 1004.1.2 TAKES A OCCUPANT
 LOAD FACTOR OF 100 GROSS OR 4,500S. F./ 100= 45
 OCCUPANTS.
  
 1D) PLEASE UPDATE PLANS FOR THE HEADING MAXIMUM COMMON
 PATH OF TRAVEL LISTING FBC TABLE 1014.3. PLEASE REVIEW
 THE 2017 FBC-B TABLE 1006.2.1 FOR COMMON PATH OF
 TRAVEL.
  
 1E)(1) THE RESTROOM # 2 SHOWS THE DOOR SWINGING OUT
 INTO THE EGRESS PATH BLOCKING THE DOORWAY/ EGRESS PATH
 TO THE SAMPLE ROOM AND THE EXIT DISCHARGE. PLEASE
 REVIEW SECTION 1005.7.1DOOR SWINGS.
  
 1E)(2) THE RESTROOM # 2 DOOR CAN SWING INTO A SINGLE
 TOILET USER ROOM. TOILET ROOM DOORS. 2017
 FBC-ACCESSIBILITY CODE FIGURE 604.8.1.6 SHOWS AN
 OUTSWING DOOR. PLEASE ALSO REVIEW SECTION 603.2.3.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCES REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 PLEASE SEE EXCEPTION 2. WHERE TOILET ROOMS ARE FOR
 INDIVIDUAL USE AND A CLEAR FLOORS SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING. WHAT WOULD NEED TO BE SHOWN FOR THE INSWING
 DOOR IS THE REQUIRED 30X48 INCH CLEAR FLOOR SPACE
 BEYOND THE ARC OF THE DOOR. USUALLY AT A 45% ANGLE TO
 THE DOOR ENTRANCE.
  
 1F) SHEET A05 SHOWS A BREAK ROOM BUT THERE ARE NO
 DETAILS OR ELEVATIONS OF THIS AREA, THE PLANS DO NOT
 SHOW HOW ACCESSIBILITY IS GOING TO BE MET, FRONT
 APPROACH OR SIDE APPROACH AND COUNTER HEIGHT.
 606 LAVATORIES AND SINKS> 2017 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED,
 SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED CLEAR FLOOR
 SPACE ON THE FLOOR PLAN.
  
 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 1G) THE FLOOR PLAN IS ALSO MISSING DRINKING FOUNTAINS.
  
 1G)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 1G)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 1G)(3) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 1G)(4) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 1G)(5) 211.3 MORE THAN MINIMUM NUMBER. WHERE MORE THAN
 THE MINIMUM NUMBER OF DRINKING FOUNTAINS SPECIFIED IN
 211.2ARE PROVIDED, 50 PERCENT OF THE TOTAL NUMBER OF
 DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND 50 PERCENT SHALL OF THE TOTAL NUMBER
 OF DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.7.
  
 2) I COULD NOT FIND A ROOM FINISH SCHEDULE BUT HERE IS
 IMPORTANT CODE INFORMATION THAT NEEDS TO BE
 INCORPORATED INTO YOUR PLANS. 2017 FBC-B 1210.2.2.
 WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE
 BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY
 PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 3) THE FLOOR PLAN AND ELEVATION PLAN PROVIDE THE
 PRESSURES FOR THE WINDOWS AND DOORS BUT THEY ARE
 MISSING FOR THE ROOF. SHEET A01 INDICATES NEW RECOVER
 LOW SLOPED ROOF MEMBRANE OVER THE EXISTING CONCRETE
 STRUCTURAL ROOF. PLEASE PROVIDE THE PRESSURES FOR ROOF
 ZONES 1, 2 AND 3.
  
 3A) PLEASE ALSO NOTE ON SHEET A01 WHAT IS THE HEIGHT OF
 THE EXISTING PARAPET. IF THERE IS ANY AT ALL.
  
 3B) THE PLAN DOES NOT ADDRESS ROOF DRAINAGE AT ALL.
 2017 FBC-B 1503.4. SCUPPERS AND OVERFLOWS VS ROOF
 DRAINS.
  
 3C) PLEASE TAKE NOTE FOR RECOVER ROOFS THAT ARE ADHERED
 TO CONCRETE ROOF SLABS. PULL TEST ARE REQUIRED AND
 FIELD INSPECTOR VERIFICATION THAT THE ROOFS ARE IN A
 CONDITION THAT CAN BE RECOVERED .SEE REQUIREMENTS FOUND
 IN THE 2017 EXISTING BUILDING CODE 706.3 RECOVERING
 VERSES REPLACEMENT.
  
 4) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
 (G) PRE-ENGINEERED A/C STANDS
  
 5A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 5C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 5D) DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 8) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  