2020-12-14 16:16:0012/14/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE LIFE SAFETY L-1 PLAN, IT SHOWS A DOUBLE
 DRINKING FOUNTAIN, AND ON MP-1 AND E-1, IT SHOWS A
 SINGLE PLEASE CORRECT, AND PLEASE SHOW THE FORWARD
 APPROACH AS IT IS A HIGH AND LOW PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. PLEASE SHOW THE CLEAR FLOOR SPACE FOR LAV ON THE
 CORRECT SIDE. THE LAV WAS MOVED AND NOT THE CLEAR FLOOR
 SPACE LAYOUT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE UPDATE THE PROVISOS THAT ARE APPROVED IN
 VERSION ONE PLANS;
  
 A. TEMPERED WATER DEVICE ON LAV THAT COMPLIES WITH ASSE
 1070 PER THE 2017 FBC SEC. P 607.4.
  
 B. WATER SERVICE SUPPLY AND SHUT OFF VALVES FOR
 DRINKING FOUNTAIN ON ISOMETRIC PER 2017 FBC SEC. P
 306.4.
  
 C. HAMMER ARRESTORS FOR DRINKING FOUNTAIN PER THE 2017
 FBCSE. 604.9.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR