Plan Review Notes
Plan Review Notes For Permit 20110271
Permit Number 20110271
Review Stop B
Sequence Number 3
Notes
Date Text
2021-06-02 11:40:53WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110271
 ADD: 2300 45TH ST.
 CONT: TBD/TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 3RD REVIEW
 DATE: WED. JUNE 02ND/ 2021
 ACTION: BUILDING PASSED/ PROVISOS
  
 1) NOTE ONLY. THIS MAIN BUILDING PERMIT WILL INCLUDE
 THE REVIEWS FOR THE MECHANICAL, ELECTRICAL, PLUMBING &
 ROOFING PERMITS. REVIEWS AND ASSOCIATED FEES FOR ALL
 OTHER PERMITS ARE NOT INCLUDED UNDER THIS PERMIT.
 SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLER, FIRE
 ALARM, RACK STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR
 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK
 IN COOLERS & FREEZERS, CANOPIES, ALL LOW VOLTAGE
 PERMITS, GENERATORS & FUEL TANKS WITH FILL STATIONS,
 GAS PERMIT, POOL, JACUZZI AND ASSOCIATED SUB-PERMITS,
 AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, LANDSCAPE,
 IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR
 STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND
 ASSOCIATED FEES WITH EACH PERMIT.
  
 2) BUILDING PROVISO: SHEET S3-0 THE ROOF FRAMING PLAN
 SHOWS BOTH WELDED AND OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 3) DEFERRED SUBMITTAL. SHEET S6-0 THERE ARE 3 OPTIONS
 FOR ANCHORING THE OF THE ROOF TOP CURB TO THE ROOF
 FRAMING.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  