2020-11-30 07:58:21 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20110271 |
| ADD: 2300 45TH ST. |
| CONT: TBD/TO BE DETERMINED |
| TEL: ??? |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: 11/30/2020 |
| ACTION: DENIED |
| |
| 1) THIS MAIN BUILDING PERMIT WILL INCLUDE THE REVIEWS |
| FOR THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING |
| PERMITS. REVIEWS AND ASSOCIATED FEES FOR ALL OTHER |
| PERMITS ARE NOT INCLUDED UNDER THIS PERMIT. |
| SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLER, FIRE |
| ALARM, RACK STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR |
| ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK |
| IN COOLERS & FREEZERS, CANOPIES, ALL LOW VOLTAGE |
| PERMITS, GENERATORS & FUEL TANKS WITH FILL STATIONS, |
| GAS PERMIT, POOL, JACUZZI AND ASSOCIATED SUB-PERMITS, |
| AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, LANDSCAPE, |
| IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR |
| STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND |
| ASSOCIATED FEES WITH EACH PERMIT. |
| |
| 2) THE COVERSHEET LIST ALL PRODUCT APPROVALS FOR |
| COMPONENTS AND CLADDING FOR THIS BUILDING. PLEASE NOTE |
| THAT NONE OF THE SUBMITTED PRODUCT APPROVALS SHOW |
| COMPLIANCE WITH W. P. B. 107.3.4. PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| REVIEWS FOR ALL PRODUCT APPROVALS WILL NOT OCCUR UNTIL |
| COMMENTS 2-5 ARE ADDRESSED. PLEASE ALSO NOTE SINCE THE |
| SUBMITTED PRODUCT APPROVALS ARE BEING REVIEWED BEFORE |
| PERMIT ISSUANCE ANY CHANGE IN PRODUCT APPROVALS WILL BE |
| A REVISION FOR EACH PRODUCT. |
| |
| 3) PRODUCT APPROVALS WITH GLAZING UNITS, IDENTIFY |
| GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT |
| APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH |
| IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| THE TESTS. |
| |
| 4) KAWNEER STOREFRONT PRODUCT APPROVAL FL8787-R9 ONLY |
| THE 3 FRONT PAGES OF THE REPORT WERE UPLOADED, NONE OF |
| THE TECHNICAL PAGES WERE LOADED. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 5) PLEASE BE AWARE OF THE CURRENT FLORIDA PRODUCT |
| APPROVAL FL14207-R20 FOR SYSTEM SC-210 HAS A DIFFERENT |
| GRADE STEEL DECK AND LOWER PRESSURES -30.0 PSF. THE |
| CURRENT PRODUCT APPROVAL ON THE STATE WEBSITE IS TO BE |
| USED. DIFFERENCE IN PRODUCT APPROVALS. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 6A) SHEET S1-0 UNDER THE HEADING FOUNDATION/ EARTHWORKS |
| LIST A SOILS REPORT ESC PROJECT # 25:3387-A DATED |
| 11-26TH /2019, THIS REPORT WAS NOT SUBMITTED IN THIS |
| REVIEW. QUESTIONABLE SOILS. 1803.5.2 QUESTIONABLE SOIL. |
| WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 6B) DOES THE SOILS REPORT ADDRESS CONCERNS ABOUT THE |
| UNDERGROUND STORAGE TANKS AND CLOSENESS OF CANALS AND |
| UNDER GROUND WATER. TO DATE THERE HAS BEEN NO SOILS |
| REPORT SUBMITTED AS TO THE WATER TABLE LEVEL, AND HOW |
| OR IF DEWATERING WILL BE REQUIRED AT THIS SITE SINCE |
| THERE IS A CANAL JUST WEST OF THIS PROPERTY. |
| |
| 6C) DOES THE SOILS REPORT ADDRESS THE CONCERNS ABOUT |
| 2017 FBC-B 1804.1. EXCAVATION NEAR FOUNDATIONS. |
| EXCAVATION FOR ANY PURPOSE SHALL NOT REDUCE THE LATERAL |
| SUPPORT FROM ANY FOUNDATION OR ADJACENT FOUNDATION |
| WITHOUT FIRST UNDERPINNING OR PROTECTING THE FOUNDATION |
| AGAINST DETRIMENTAL LATERAL OR VERTICAL MOVEMENT, OR |
| BOTH. |
| |
| 7) NO ACTION NEEDED. COMPONENTS & CLADDING PRESSURES |
| FOUND ON S1-0 ARE GOOD IN VASD. |
| |
| 8) SHEET S3-0 THE ROOF FRAMING PLAN SHOWS BOTH WELDED |
| AND OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED |
| TO PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER |
| OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| FRAMING INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| AT 561-805-6666. |
| |
| 9) SHEET S3-0 IN THE BOTTOM LEFT CORNER OF THE PAGE |
| METAL DECK ATTACHMENT SCHEDULE. SHEET S6-0 OFFERS 3 |
| METAL DECK TYPE 22-GAUGE, 20-GAUGE & 18-GAUGE DECKING. |
| UNDER THE SIDE LAP FASTENER THERE IS GIVEN OPTIONS AS |
| TO FASTENER TYPE AND GAUGE OF METAL. PLEASE NOTE THAT |
| THE GAUGE OF ROOFING METAL DOES NEED TO MATCH THAT OF |
| THE ROOFING PRODUCT APPROVAL AND ANCHORS. PLEASE SEE |
| CITY AMENDMENT FOR OPTIONS, NO OPTIONS. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B. |
| ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS |
| SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE |
| TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A |
| WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION, NO OPTIONS". CONSTRUCTION DOCUMENTS SHALL |
| BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 10) SHEET 6-0 THERE ARE 2 OPTIONS FOR ANCHORING THE OF |
| THE ROOF TOP CURB TO THE ROOF FRAMING. IN BOTH MOUNTING |
| OPTIONS OF THE RTU TO THE ROOF TOP CURB, PRE-ENGINEERED |
| RTU TIE-DOWNS TO FBC/ ASCE 7-10 BY SPECIALTY ENGINEER |
| SIZE, QUANTITY AND PLACEMENT OF TIE-DOWNS SHALL BE |
| REQUIRED BY THE TIE DOWN SUPPLIER FOR EACH RTU. GC TO |
| SUBMIT SIGNED AND SEALED TIE-DOWN ENGINEERING & DETAILS |
| FOR REVIEW AND APPROVAL BY THE DESIGNER OF RECORD |
| BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 11) SHEET A3-1 DETAIL 9 CONDENSING UNIT ROOF SUPPORT |
| DETAIL REFERS TO ALUMINUM A/C STAND (MIAMI TECH) EITHER |
| MIAMI-DADE NOA OR FLORIDA APPROVAL. PLEASE PROVIDE THE |
| PRODUCT APPROVAL OF CHOICE AND PLEASE PROVIDE |
| COMPLIANCE WITH: |
| THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |