2020-11-30 07:58:21WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110271
 ADD: 2300 45TH ST.
 CONT: TBD/TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: 11/30/2020
 ACTION: DENIED
  
 1) THIS MAIN BUILDING PERMIT WILL INCLUDE THE REVIEWS
 FOR THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING
 PERMITS. REVIEWS AND ASSOCIATED FEES FOR ALL OTHER
 PERMITS ARE NOT INCLUDED UNDER THIS PERMIT.
 SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLER, FIRE
 ALARM, RACK STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR
 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK
 IN COOLERS & FREEZERS, CANOPIES, ALL LOW VOLTAGE
 PERMITS, GENERATORS & FUEL TANKS WITH FILL STATIONS,
 GAS PERMIT, POOL, JACUZZI AND ASSOCIATED SUB-PERMITS,
 AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, LANDSCAPE,
 IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR
 STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND
 ASSOCIATED FEES WITH EACH PERMIT.
  
 2) THE COVERSHEET LIST ALL PRODUCT APPROVALS FOR
 COMPONENTS AND CLADDING FOR THIS BUILDING. PLEASE NOTE
 THAT NONE OF THE SUBMITTED PRODUCT APPROVALS SHOW
 COMPLIANCE WITH W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 REVIEWS FOR ALL PRODUCT APPROVALS WILL NOT OCCUR UNTIL
 COMMENTS 2-5 ARE ADDRESSED. PLEASE ALSO NOTE SINCE THE
 SUBMITTED PRODUCT APPROVALS ARE BEING REVIEWED BEFORE
 PERMIT ISSUANCE ANY CHANGE IN PRODUCT APPROVALS WILL BE
 A REVISION FOR EACH PRODUCT.
  
 3) PRODUCT APPROVALS WITH GLAZING UNITS, IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 4) KAWNEER STOREFRONT PRODUCT APPROVAL FL8787-R9 ONLY
 THE 3 FRONT PAGES OF THE REPORT WERE UPLOADED, NONE OF
 THE TECHNICAL PAGES WERE LOADED. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) PLEASE BE AWARE OF THE CURRENT FLORIDA PRODUCT
 APPROVAL FL14207-R20 FOR SYSTEM SC-210 HAS A DIFFERENT
 GRADE STEEL DECK AND LOWER PRESSURES -30.0 PSF. THE
 CURRENT PRODUCT APPROVAL ON THE STATE WEBSITE IS TO BE
 USED. DIFFERENCE IN PRODUCT APPROVALS. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6A) SHEET S1-0 UNDER THE HEADING FOUNDATION/ EARTHWORKS
 LIST A SOILS REPORT ESC PROJECT # 25:3387-A DATED
 11-26TH /2019, THIS REPORT WAS NOT SUBMITTED IN THIS
 REVIEW. QUESTIONABLE SOILS. 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 6B) DOES THE SOILS REPORT ADDRESS CONCERNS ABOUT THE
 UNDERGROUND STORAGE TANKS AND CLOSENESS OF CANALS AND
 UNDER GROUND WATER. TO DATE THERE HAS BEEN NO SOILS
 REPORT SUBMITTED AS TO THE WATER TABLE LEVEL, AND HOW
 OR IF DEWATERING WILL BE REQUIRED AT THIS SITE SINCE
 THERE IS A CANAL JUST WEST OF THIS PROPERTY.
  
 6C) DOES THE SOILS REPORT ADDRESS THE CONCERNS ABOUT
 2017 FBC-B 1804.1. EXCAVATION NEAR FOUNDATIONS.
 EXCAVATION FOR ANY PURPOSE SHALL NOT REDUCE THE LATERAL
 SUPPORT FROM ANY FOUNDATION OR ADJACENT FOUNDATION
 WITHOUT FIRST UNDERPINNING OR PROTECTING THE FOUNDATION
 AGAINST DETRIMENTAL LATERAL OR VERTICAL MOVEMENT, OR
 BOTH.
  
 7) NO ACTION NEEDED. COMPONENTS & CLADDING PRESSURES
 FOUND ON S1-0 ARE GOOD IN VASD.
  
 8) SHEET S3-0 THE ROOF FRAMING PLAN SHOWS BOTH WELDED
 AND OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED
 TO PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER
 OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 9) SHEET S3-0 IN THE BOTTOM LEFT CORNER OF THE PAGE
 METAL DECK ATTACHMENT SCHEDULE. SHEET S6-0 OFFERS 3
 METAL DECK TYPE 22-GAUGE, 20-GAUGE & 18-GAUGE DECKING.
 UNDER THE SIDE LAP FASTENER THERE IS GIVEN OPTIONS AS
 TO FASTENER TYPE AND GAUGE OF METAL. PLEASE NOTE THAT
 THE GAUGE OF ROOFING METAL DOES NEED TO MATCH THAT OF
 THE ROOFING PRODUCT APPROVAL AND ANCHORS. PLEASE SEE
 CITY AMENDMENT FOR OPTIONS, NO OPTIONS.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION, NO OPTIONS". CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 10) SHEET 6-0 THERE ARE 2 OPTIONS FOR ANCHORING THE OF
 THE ROOF TOP CURB TO THE ROOF FRAMING. IN BOTH MOUNTING
 OPTIONS OF THE RTU TO THE ROOF TOP CURB, PRE-ENGINEERED
 RTU TIE-DOWNS TO FBC/ ASCE 7-10 BY SPECIALTY ENGINEER
 SIZE, QUANTITY AND PLACEMENT OF TIE-DOWNS SHALL BE
 REQUIRED BY THE TIE DOWN SUPPLIER FOR EACH RTU. GC TO
 SUBMIT SIGNED AND SEALED TIE-DOWN ENGINEERING & DETAILS
 FOR REVIEW AND APPROVAL BY THE DESIGNER OF RECORD
 BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 11) SHEET A3-1 DETAIL 9 CONDENSING UNIT ROOF SUPPORT
 DETAIL REFERS TO ALUMINUM A/C STAND (MIAMI TECH) EITHER
 MIAMI-DADE NOA OR FLORIDA APPROVAL. PLEASE PROVIDE THE
 PRODUCT APPROVAL OF CHOICE AND PLEASE PROVIDE
 COMPLIANCE WITH:
 THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  