Date |
Text |
2020-12-18 11:25:58 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| |
| ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW. |
| |
| 1) SCOPE OF ELECTRICAL WORK IS NOT CLEAR. ELECTRICAL |
| SHEET E5-0 CONTAINS MANY PANEL SCHEDULES, BUT NO |
| REFERENCE IS MADE TO WHAT IS INCLUDE ON THIS PERMIT AND |
| THAT SEEM TO HAVE NO RELATION TO THIS PERMIT. PLEASE |
| SUBMIT ELECTRICAL DRAWINGS THAT SHOW THE SPECIFIC |
| ELECTRICAL WORK TO BE DONE UNDER THIS PERMIT. FBC 107 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| ENRIQUE QUINONEZ |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |