2020-11-19 13:28:10 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| THE FOLLOWING TEST REPORTS ARE REQUIRED: |
| |
| FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1) THE TEST REPORT FOR STRUCTURE-BORNE SOUND, ASTM E |
| 492-09, IS A BLANK PAGE. FBC1207.3 |
| |
| 2) THE REQUIRED FLAME SPREAD TEST REPORT FOR THE SOUND |
| INSULATION, ASTM E 84-09, WAS NOT SUBMITTED. FBC 603.1 |
| |
| 3) THE TEST REPORTS WILL HAVE TO CLEARLY IDENTIFY THE |
| PRODUCT THAT IS BEING TESTED IN ORDER TO VERIFY THAT IT |
| IS THE PRODUCT THAT WILL BE INSTALLED. FBC 107.2.1 |
| |
| |