Plan Review Notes For Permit 20110213 |
Permit Number |
20110213 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-01-05 17:41:34 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW APPROVED WITH PROVISOS: | | | | THE ENGINEER HAS CLARIFIED THE DIMENSIONS (3/8"X6"X6") | | OF THE PLATES SHOWN ON DETAIL 3 OF PAGE C10. | | | | AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | BE USED. | | AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. | | |
|