Plan Review Notes
Plan Review Notes For Permit 20110213
Permit Number 20110213
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-28 12:01:46PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE MORE DETAIL/CLARIFY THE
 FOLLOWING:
  
 1) PAGE C10, THE WELDED CONNECTIONS FOR THE MOUNT BRACE
 ARE NOT CLEAR AS DETAIL #3 IDENTIFIES A 3/8" THICK
 PLATE BY 6' LONG BY 6" WIDE IN TWO LOCATIONS ALONG THE
 BOTTOM OF CONNECTION AREAS. THE WELDS ARE IDENTIFIED AS
 3/16" FILLET WELDS BOTH SIDES OF WHAT APPEARS TO BE
 VERTICAL PLATE TO PLATE CONNECTIONS.
  
 2) PAGE C11, THE SERVICE PLATFORM EXTENSION (DETAILS 1
 & 2) ARE NOT SPECIFIC IN THE NUMBER OF 1/4" THRU BOLTS,
 1/2" SQUARE U-BOLTS, 3"X3"X1/4" HSS ANGLES, & 12"X1
 1/2" PERF-O-GRIP PLANKS. THESE ITEMS ALL HAVE ONLY A
 TYPICAL QUANTITY. PLEASE PROVIDE SPECIFIC QUANTITIES
 FOR EACH ITEM.