Plan Review Notes For Permit 20110213 |
Permit Number |
20110213 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-28 12:01:46 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, PLEASE PROVIDE MORE DETAIL/CLARIFY THE | | FOLLOWING: | | | | 1) PAGE C10, THE WELDED CONNECTIONS FOR THE MOUNT BRACE | | ARE NOT CLEAR AS DETAIL #3 IDENTIFIES A 3/8" THICK | | PLATE BY 6' LONG BY 6" WIDE IN TWO LOCATIONS ALONG THE | | BOTTOM OF CONNECTION AREAS. THE WELDS ARE IDENTIFIED AS | | 3/16" FILLET WELDS BOTH SIDES OF WHAT APPEARS TO BE | | VERTICAL PLATE TO PLATE CONNECTIONS. | | | | 2) PAGE C11, THE SERVICE PLATFORM EXTENSION (DETAILS 1 | | & 2) ARE NOT SPECIFIC IN THE NUMBER OF 1/4" THRU BOLTS, | | 1/2" SQUARE U-BOLTS, 3"X3"X1/4" HSS ANGLES, & 12"X1 | | 1/2" PERF-O-GRIP PLANKS. THESE ITEMS ALL HAVE ONLY A | | TYPICAL QUANTITY. PLEASE PROVIDE SPECIFIC QUANTITIES | | FOR EACH ITEM. |
|