2020-11-20 15:54:24 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20110201 |
| 11/20/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE LP TANK AND ANODE BANK INSTALLATION DETAIL SHALL |
| BEAR THE DIGITAL SIGNATURE AND SEAL OF THE ENGINEER WHO |
| PREPARED THE DRAWING- FL. STATUTE 471.025 AND SECTION |
| 61G15-23.005 FAC. AS AN ALTERNATIVE TO PROVIDING AN |
| ORIGINAL SIGNED AND SEALED DRAWING, A PAPER VERSION OF |
| THE DRAWING CAN BE SUBMITTED TO THE WPB BUILDING DEPT. |
| WHEN ALL OTHER REVIEWS ARE APPROVED. PLEASE REVISE THE |
| DRAWING TO SHOW THE TANK BURIAL DEPTH, ANCHORING BASE |
| MATERIAL AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| CABLES OR STRAPS. |
| |
| 2) GAS RISER: PROVIDE AN ENLARGED DETAIL SHOWING THE |
| LOW PRESSURE REGULATOR, OUTLET PRESSURE, REQUIRED PIPE |
| UNIONS, DRIP LEG AND FLEX CONNECTOR TO THE GENERATOR- |
| SECTIONS G2421.1, G2421.2(7), G2419.2, & G2422.1 FBC |
| RES. |
| |
| 3) SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS |
| SHOWING THE SELECTED MODEL, THE MAX INLET AND OUTLET |
| SIZE AND PRESSURES, AND ORIFICE SIZE- SECTION G2421.1 & |
| G2421.2 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |