2020-11-06 11:26:37BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 1- SECTION 1/S-1:
 A) DETAIL SHOWS A NEW FASCIA. WITH A NOTE STATING "(N)
 SHEATHING (SEE ARCH)". THERE ARE NOT ARCHITECTURAL
 DRAWINGS SUBMITTED. PROVIDE THE ARCHITECTURAL DRAWING
 WITH COMPLETE SHEATHING SPECIFICATIONS OR PROVIDE
 COMPLETE SPECIFICATIONS (TYPE, FASTENING, ETC).
 SEC. 702.6 FBC-EXISTING BUILDING. SEC. 1609.1
 FBC-BUILDING.
  
 B) DETAIL SHOWS "(E) ROOF COVERING MEMBRANE. (SEE ARCH
 FOR NEW ROOFING /FLASHING)". THERE ARE NOT
 ARCHITECTURAL DRAWINGS SUBMITTED. PROVIDE THE
 ARCHITECTURAL DRAWING WITH COMPLETE ROOFING
 SPECIFICATIONS OR PROVIDE COMPLETE SPECIFICATIONS
 (TYPE, FASTENING, ETC).
 SEC. 702.6 FBC-EXISTING BUILDING. SEC. 1609.1
 FBC-BUILDING.
  
 2- CLARIFY NOTE #4 OF EXISTING PARTIAL ROOF FRAMING
 PLAN. DESIGN PRESSURES SEEM TO BE LOW FOR A BUILDING
 LOCATED IN EXPOSURE "D" AS SPECIFIED ON WIND LOAD NOTE
 1(A) UNDER THE STRUCTURAL NOTES. REVISE/CLARIFY AS
 REQUIRED. ARE THESE NOMINAL LOADS. ARE THESE THE MAIN
 WINDFORCE RESISTING FORCES. ARE THESE THESE DESIGN
 PRESSURES FOR COMPONENTS AND CLADDING?. IF SO SPECIFY
 THE ROOF ZONES AND THE WALL ZONES.
 SEC. 702.6 FBC-EXISTING BUILDING. SEC. 1609.1
 FBC-BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PRODUCT APPROVALS:
 A)PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR FLAT ROOF ASSEMBLY. AND, CLEARLY
 IDENTIFY THE SPECIFIC ASSEMBLY TO BE INSTALLED.
  
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL).
  
 B) ROOFING SUBMIT REQUIRED. SEC. 105.1 CITY AMENDMENTS.
  
 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved