Date |
Text |
2020-11-17 13:49:47 | PLAN REVIEW GENERATOR / BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2) STRUCTURAL PAD DETAIL SHALL BE SIGNED BY DESIGNER. |
| FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| 481, F.S. & 61G1. |
| |
| 3) ADJUST THE LOCATION OF THE GENERATOR ON THE SURVEY. |
| GENERATOR SHALL BE LOCATED PER R303.5.1. |
| R303.5.1 INTAKE OPENINGS. |
| MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS |
| SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM |
| ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, |
| CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS |
| AND LOADING DOCKS. |
| |
| PROVIDE SETBACK DIMENSIONS TO PROPERTY LINES, BUILDING |
| AND BUILDING OPENINGS PER PER 107.2 CONSTRUCTION |
| DOCUMENTS. |
| |
| 4) PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). TOP OF GENERATOR PAD SHALL BE AT OR ABOVE 8.0 |
| FEET NAVD. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |