Plan Review Notes
Plan Review Notes For Permit 20110155
Permit Number 20110155
Review Stop B
Sequence Number 2
Notes
Date Text
2021-07-01 10:08:07PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIED. [THE GENERATOR PAD DRAWING THAT WAS
 SUBMITTED IS NOT SIGNED AND SEALED BY THE ENGINEER AND
 IS ILLEGIBLE. FS 471 AND FBC AMEND. 107.2.1] SUBMIT
 GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD ANCHORING
 DETAILS. PRE-FABRICATED GENERATOR PADS REQUIRE PRODUCT
 APPROVALS OR SITE SPECIFIC ENGINEERING. FBC AMENDMENTS
 107.2.1
  
 2) NOT COMPLIED. SUBMIT A SITE PLAN THAT SHOWS THE
 LOCATION OF THE GENERATOR. FBC AMEND.107
  
 3) NOT COMPLIED. THE GENERATOR EXHAUST IS REQUIRED TO
 BE 10 FEET FROM OPENINGS TO A STRUCTURE INCLUDING
 GARAGES. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  