2021-03-04 15:13:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. PRE-FABRICATED GENERATOR PADS
 REQUIRE PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING.
 FBC AMENDMENTS 107.2.1
 2) SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE
 GENERATOR. FBC AMEND.107
 3) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 OPENINGS TO A STRUCTURE INCLUDING GARAGES. FBC-R303.5.1
 INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS.
  