2020-11-25 11:07:462ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20110141
 11/25/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED GAS RISER SHOWS AN EXISTING LINE TO
 INTERIOR APPLIANCES- WATER HEATER, DRYER AND COOKTOP.
 THE WATER HEATER WAS INSTALLED UNDER PERMIT 16040206
 HOWEVER IT WAS NEVER INSPECTED.THE PERMIT IS EXPIRED
 AND AS A RESULT THE PERMIT MUST BE REISSUED SO
 INSPECTIONS OF THE GAS AND WATER PIPING CAN BE
 ACCOMPLISHED. PLEASE CONTACT [email protected] FOR
 MORE INFORMATION. CONCERNING THE DRYER AND THE COOKTOP,
 I AM UNABLE TO FIND RECORDS OF PERMITS FOR THE
 INSTALLATIONS INCLUDING THE GAS PIPING TO THE
 APPLIANCES, AND THE REQUIRED COMBUSTION AIR AND VENTING
 OF THE APPLIANCES. PLEASE PROVIDE A COMPLETE RISER
 DRAWING THAT SHOWS THE INTERIOR GAS PIPING BRANCH
 INCLUDING THE TOTAL LENGTH OF THE RUN, CUT LENGTH
 SIZES, AND THE TYPES AND SIZES OF GAS PIPING- SECTIONS
 G2413.4.1 AND G2413.4.2 FBC RES. PLEASE NOTE ROUGH AND
 FINAL INSPECTIONS OF THE PIPING SYSTEM WILL BE
 REQUIRED- SECTION 110.1 WPB.
  
 2) PROVIDE A FLOOR PLAN LAYOUT THAT SHOWS THE LOCATIONS
 OF THE INTERIOR APPLIANCES. INDICATE HOW COMBUSTION AIR
 IS BEING PROVIDED TO THE WATER HEATER AND COOKTOP, AND
 MAKEUP AIR FOR THE DRYER- SECTION G2407.1 FBC RES.
  
 3) PROVIDE VENTING SPECIFICATIONS AND DIAGRAMS FOR THE
 APPLIANCES- SECTIONS G2408.1, G2427.1, G2439.3, AND
 M1503 FBC RES.
  
 4) ADJUST THE PERMIT VALUE TO INCLUDE THE COSTS OF
 ADDITIONAL WORK REQUIRED FOR LEGAL PERMITTING OF THE
 GAS PIPING SYSTEM AND APPLIANCES- SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  