2020-11-19 07:50:32 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20110141 |
| 11/18/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REVISE THE RISER DRAWING TO SHOW THE BRANCH LINE |
| INTO THE RESIDENCE SUPPLYING THE WATER HEATER INSTALLED |
| UNDER PERMIT 16040206, AND ALL OTHER INTERIOR |
| APPLIANCES- SECTIONS G2412.3 & G2412.4 FBC RES. PER THE |
| PERMIT RECORDS, THE WATER HEATER IS A 50 GALLON, 40,000 |
| BTUH UNIT. |
| |
| 2) REVISE THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF |
| THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. |
| |
| 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| FIREPIT MARKED UP OR HIGHLIGHTED TO SHOW THE BTUH LOAD, |
| INPUT PRESSURE, AND UL OR ANSI STANDARD LISTING NUMBER- |
| SECTION 107.2.1 WPB. |
| |
| 4) ADJUST THE $1800.00 PERMIT VALUE TO INCLUDE THE COST |
| OF THE FIREPIT- SECTION 109.3 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |