Plan Review Notes
Plan Review Notes For Permit 20110097
Permit Number 20110097
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-10 13:43:43JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.1. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE.
 2. FBC B 1609. PROVIDE A COMPLETE SET OF SIGNED AND
 SEALED DESIGN PRESSURE CALCULATIONS FOR HIGH
 RISE/COMMERCIAL BUILDINGS BY A FLORIDA REGISTERED
 DESIGN PROFESSIONAL. DESIGN PRESSURE CALCULATIONS MUST
 BE SPECIFIC FOR EACH OPENING.
 3. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?WALL PRESSURE?; PROVIDE THE ACTUAL [PSF] FROM
 THE REVISED DESIGN PRESSURE CALCULATIONS. PLEASE
 CORRECT COLUMN HEADING ?ANCHOR SPACING?; USE CORRECT
 DESIGN PRESSURE CALCULATIONS TO DETERMINE CORRECT
 SPACING.
  