Plan Review Notes For Permit 20110091 |
Permit Number |
20110091 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-12 14:22:14 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED | | | | 1) ELECTRICAL RISER DIAGRAM INDICATES THAT A NEW METER, | | NEW MCB, AND NEW ELECTRICAL PANEL ARE BEING INSTALLED | | WHILE REST OF ELECTRICAL NOTES INDICATES THAT PANEL IS | | EXISTING AND NEW CIRCUITS ARE CONNECTED TO SPARE | | SPACES. PLEASE CLARIFY AND MODIFY RISER IF NEEDED. IF | | INSTALLING NEW PANEL, PLEASE PROVIDE COMPLETE PANEL | | SCHEDULE. | | 2) RECEPTACLES IN GARAGE NEED TO BE GFCI PROTECTED. NEC | | 210.8 FBC RE E3902.2 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|