Plan Review Notes
Plan Review Notes For Permit 20110091
Permit Number 20110091
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-12 14:22:14CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED
  
 1) ELECTRICAL RISER DIAGRAM INDICATES THAT A NEW METER,
 NEW MCB, AND NEW ELECTRICAL PANEL ARE BEING INSTALLED
 WHILE REST OF ELECTRICAL NOTES INDICATES THAT PANEL IS
 EXISTING AND NEW CIRCUITS ARE CONNECTED TO SPARE
 SPACES. PLEASE CLARIFY AND MODIFY RISER IF NEEDED. IF
 INSTALLING NEW PANEL, PLEASE PROVIDE COMPLETE PANEL
 SCHEDULE.
 2) RECEPTACLES IN GARAGE NEED TO BE GFCI PROTECTED. NEC
 210.8 FBC RE E3902.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved