Plan Review Notes
Plan Review Notes For Permit 20110018
Permit Number 20110018
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-13 03:55:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO SMOKE/CARBON MONOXIDE ALARMS SHOWN
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
  
 2) ALL OUTLETS IN THE GARAGE 120V SHALL BE GFCI
 PROTECTED.
 E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES
 INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF
 UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK
 AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(2)]
  
 3) OUTLETS NEEDED AT FRONT AND REAR OF RESIDENCE.
 FOR A ONE FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT
 MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING. NEC
 210.52(E)(1) FBC RE3901.7
  
 4) OUTLETS FOR THE LAUNDRY AREA TO BE AFCI AND GFCI
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.16
  
 5) ISLAND NEEDS ANOTHER OUTLET ON DISHWASHER END FOR
 COUNTER SPACE RECEPTACLES.
 COUNTERTOP SPACES SEPARATED BY RANGETOPS,
 REFRIGERATORS, OR SINKS SHALL BE CONSIDERED AS SEPARATE
 COUNTERTOP SPACES IN APPLYING THE REQUIREMENTS OF
 210.52(C)(1). IF A RANGE, COUNTER-MOUNTED COOKING UNIT,
 OR SINK IS INSTALLED IN AN ISLAND OR PENINSULAR
 COUNTERTOP AND THE DEPTH OF THE COUNTERTOP BEHIND THE
 RANGE, COUNTER-MOUNTED COOKING UNIT, OR SINK IS LESS
 THAN 300 MM (12 IN.), THE RANGE, COUNTER-MOUNTED
 COOKING UNIT, OR SINK SHALL BE CONSIDERED TO DIVIDE THE
 COUNTERTOP SPACE INTO TWO SEPARATE COUNTERTOP SPACES.
 EACH SEPARATE COUNTERTOP SPACE SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS IN 210.52(C).
  
  