2020-11-13 03:55:37 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) NO SMOKE/CARBON MONOXIDE ALARMS SHOWN |
| |
| PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE |
| EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC |
| R314.3, FBC 107.2.1 |
| |
| 2) ALL OUTLETS IN THE GARAGE 120V SHALL BE GFCI |
| PROTECTED. |
| E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES. |
| 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES |
| INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF |
| UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK |
| AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL. [210.8(A)(2)] |
| |
| 3) OUTLETS NEEDED AT FRONT AND REAR OF RESIDENCE. |
| FOR A ONE FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY |
| DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE |
| RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT |
| MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. NEC |
| 210.52(E)(1) FBC RE3901.7 |
| |
| 4) OUTLETS FOR THE LAUNDRY AREA TO BE AFCI AND GFCI |
| ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, |
| LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING |
| ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| RE3902.16 |
| |
| 5) ISLAND NEEDS ANOTHER OUTLET ON DISHWASHER END FOR |
| COUNTER SPACE RECEPTACLES. |
| COUNTERTOP SPACES SEPARATED BY RANGETOPS, |
| REFRIGERATORS, OR SINKS SHALL BE CONSIDERED AS SEPARATE |
| COUNTERTOP SPACES IN APPLYING THE REQUIREMENTS OF |
| 210.52(C)(1). IF A RANGE, COUNTER-MOUNTED COOKING UNIT, |
| OR SINK IS INSTALLED IN AN ISLAND OR PENINSULAR |
| COUNTERTOP AND THE DEPTH OF THE COUNTERTOP BEHIND THE |
| RANGE, COUNTER-MOUNTED COOKING UNIT, OR SINK IS LESS |
| THAN 300 MM (12 IN.), THE RANGE, COUNTER-MOUNTED |
| COOKING UNIT, OR SINK SHALL BE CONSIDERED TO DIVIDE THE |
| COUNTERTOP SPACE INTO TWO SEPARATE COUNTERTOP SPACES. |
| EACH SEPARATE COUNTERTOP SPACE SHALL COMPLY WITH THE |
| APPLICABLE REQUIREMENTS IN 210.52(C). |
| |
| |