Plan Review Notes For Permit 20101494 |
Permit Number |
20101494 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-05 11:06:11 | PLAN REVIEW / BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC 2014 | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE DESIGN PRESSURES OF WINDOW OPENINGS. YOU MAY | | PLACE THESE ON THE WINDOW SCHEDULE OR ON THE FLOOR PLAN | | NEXT TO EACH OPENING. | | R301.2.1 WIND DESIGN CRITERIA. | | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN | | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING | | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED | | FROM FIGURE R301.2(4). | | |
|