2020-11-19 11:45:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
  
  
  
  