Plan Review Notes
Plan Review Notes For Permit 20101488
Permit Number 20101488
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-20 16:16:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 MIXING SERVICE AND FEEDER IN SAME RACEWAY(GUTTER)
  
 230.7 OTHER CONDUCTORS IN RACEWAY OR CABLE CONDUCTORS
 OTHER THAN SERVICE CONDUCTORS SHALL NOT BE INSTALLED IN
 THE SAME SERVICE RACEWAY OR SERVICE CABLE.