2020-11-05 09:08:58 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| PERMIT- 20101457 |
| 11/5/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED |
| FOR GAS PIPING- SECTIONS 105.1 & 107.2.1 WPB. A REVIEW |
| OF THE GAS HAS NOT BEEN PERFORMED UNDER THIS PERMIT. A |
| COMPLETE GAS PLAN, RISER DRAWING, PIPE SIZING TABLES, |
| AND PIPING AND APPLIANCE SPECIFICATIONS SHALL BE |
| SUBMITTED FOR REVIEW. |
| |
| 2) SHEETS A10 & A11: PROVIDE A WATER RISER DRAWING- |
| SECTION 107.3.5.3 WPB. |
| |
| 3) A10 & A11, 1ST FLOOR RISER: THE DOUBLE LAV SINK IN |
| THE MASTER BATH REQUIRES A VENT OR THE FIXTURE DRAIN |
| MUST CONNECT HORIZONTALLY TO THE WET VENT- SECTION |
| P3108.1 FBC RES. |
| |
| 4) A11: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| TANKLESS WATER HEATER INDICATING MAKE AND MODEL AND |
| EFFICIENCY RATING- SEE TABLE C404.2 FBC EC. |
| |
| 5) A11: PLEASE MODIFY NOTE #23 TO INDICATE R-3 HOT |
| WATER PIPE INSULATION REQUIRED- SECTION R403.4 FBC EC. |
| |
| 6) A11: PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & |
| P2709.2 FBC RES. |
| |
| 7) A11: PLEASE NOTE THAT A FL. LICENSED PLUMBING |
| CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| FURTHER INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |
| |
| |