Date |
Text |
2020-11-04 07:27:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20101437 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE MORE DETAIL FOR THE SCOPE OF WORK. IS |
| THIS A LIKE FOR LIKE CHANGE OUT FOR EACH HVAC SYSTEM? |
| IF SO PLEASE SUBMIT A LIKE FOR LIKE CHANGE OUT FORM FOR |
| EACH SYSTEM. IF THIS IS NOT A LIKE FOR LIKE CHANGE OUT |
| FOR EACH SYSTEM BUT IS AN UPGRADE, THEN PLEASE SUBMIT |
| THE ENERGY CALCULATIONS AND THE EQUIPMENT SIZING |
| CALCULATIONS. FBC 107.2; FBC EC 101.5.1.1.2; FBC EC |
| R403.7; FBC RES M1401.3 |
| |
| 2) PLEASE PROVIDE DETAILS OF THE CONDENSING UNITS TIE |
| DOWN. FBC RES M1307.2 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |