Plan Review Notes
Plan Review Notes For Permit 20101437
Permit Number 20101437
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-04 07:27:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20101437
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MORE DETAIL FOR THE SCOPE OF WORK. IS
 THIS A LIKE FOR LIKE CHANGE OUT FOR EACH HVAC SYSTEM?
 IF SO PLEASE SUBMIT A LIKE FOR LIKE CHANGE OUT FORM FOR
 EACH SYSTEM. IF THIS IS NOT A LIKE FOR LIKE CHANGE OUT
 FOR EACH SYSTEM BUT IS AN UPGRADE, THEN PLEASE SUBMIT
 THE ENERGY CALCULATIONS AND THE EQUIPMENT SIZING
 CALCULATIONS. FBC 107.2; FBC EC 101.5.1.1.2; FBC EC
 R403.7; FBC RES M1401.3
  
 2) PLEASE PROVIDE DETAILS OF THE CONDENSING UNITS TIE
 DOWN. FBC RES M1307.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved