Plan Review Notes For Permit 20101427 |
Permit Number |
20101427 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-19 13:55:46 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ITEMS THAT WERE UPLOADED ARE ILLEGIBLE OR CAN | | NOT BE VIEWED. FBC 107.2.1 CONTACT THE PERMIT LIBRARIAN | | ( [email protected] ) FOR INSTRUCTIONS ON HOW TO | | UPLOAD DOCUMENTS. | | | | 2) PROVIDE THE FOLLOWING INFORMATION FOR FLOORING | | SUBMITTALS: | | 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. | | > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107. | | 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. | | 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE, | | WOOD, MARBLE, ETC.). | | 4. STATED VALUE OF WORK. | | 5. DESCRIPTION OF EXISTING SITE CONDITIONS: | | (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW | | (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ). | | 6. PROPOSED UNDERLAYMENT. | | 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON | | THE EXISTING SITE CONDITIONS. | | 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: | | E-84, E-90 & E-492. | | 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. | | (UNLESS SUBMITTING ELECTRONICALLY) | | | | | | |
|