Notes
Date Text
2020-11-05 09:19:17JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3. THE HIGHLIGHTED AREA OF PRODUCT
 APPROVAL FL16709-R6 IS NOT A ROOFING TYPE SYSTEM; YOU
 MUST CHOOSE A ROOFING TYPE SYSTEM FROM PAGES 4-14 AND
 SELECT SYSTEM NO.; EXPOSURE; ENCLOSURE; ROOF HEIGHT;
 ZONE AND ULTIMATE WIND SPEED. IF ROOFING APPLICATION
 THAT YOU ARE USING IS NOT SUPPORTED BY THIS PRODUCT
 APPROVAL YOU MUST SUBMIT A COMPLETE SET OF PRODUCT
 APPROVALS THAT DO.
  