Date |
Text |
2021-05-26 08:52:24 | ROOFING TO BE DEFERRED AT THIS TIME |
| ITEMS NEEDED FOR ROOFING SYSTEM |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) FOR AIR-PERMEABLE RAFTER SPACE INSULATION - PLEASE |
| SHOW THE RIGID BOARD OR SHEET INSULATION ON TOP OF THE |
| ROOF SHEATHING TO COMPLY WITH FBC R806.5 UNVENTED ATTIC |
| AND UNVENTED ENCLOSED RAFTER ASSEMBLIES. UNVENTED |
| ATTICS AND UNVENTED ENCLOSED ROOF FRAMING ASSEMBLIES |
| CREATED BY CEILINGS THAT ARE APPLIED DIRECTLY TO THE |
| UNDERSIDE OF THE ROOF FRAMING MEMBERS AND STRUCTURAL |
| ROOF SHEATHING APPLIED DIRECTLY TO THE TOP OF THE ROOF |
| FRAMING MEMBERS/RAFTERS, SHALL BE PERMITTED WHERE ALL |
| THE FOLLOWING CONDITIONS ARE MET: |
| |
| 5.INSULATION SHALL BE LOCATED IN ACCORDANCE WITH THE |
| FOLLOWING: |
| |
| 5.1.ITEM 5.1.1, 5.1.2, 5.1.3 OR 5.1.4 SHALL BE MET, |
| DEPENDING ON THE AIR PERMEABILITY OF THE INSULATION |
| DIRECTLY UNDER THE STRUCTURAL ROOF SHEATHING. |
| |
| 5.1.1.WHERE ONLY AIR-IMPERMEABLE INSULATION IS |
| PROVIDED, IT SHALL BE APPLIED IN DIRECT CONTACT WITH |
| THE UNDERSIDE OF THE STRUCTURAL ROOF SHEATHING. |
| |
| 5.1.2.WHERE AIR-PERMEABLE INSULATION IS PROVIDED INSIDE |
| THE BUILDING THERMAL ENVELOPE, IT SHALL BE INSTALLED IN |
| ACCORDANCE WITH SECTION 5.1.1. IN ADDITION TO THE |
| AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW THE |
| STRUCTURAL SHEATHING, RIGID BOARD OR SHEET INSULATION |
| SHALL BE INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF |
| SHEATHING IN ACCORDANCE WITH THE R-VALUES IN TABLE |
| R806.5 FOR CONDENSATION CONTROL. |
| |
| |
| 2) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA |
| STATE PRODUCT APPROVAL FOR THE ROOFING TILE - PLEASE |
| CIRCLE THE TILE ATTACHMENT TO BE USED IN THE PRODUCT |
| APPROVAL - IF USING ADHESIVE PLEASE PROVIDE THE PRODUCT |
| APPROVAL FOR THE ADHESIVE. |
| |
| |
| |