Plan Review Notes
Plan Review Notes For Permit 20101413
Permit Number 20101413
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-16 11:25:45SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE SMOKE DETECTOR LOCATIONS PER FBC
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 2) PLEASE SHOW THE VENTILATION FOR THE RAFTER SPACES
 PER FBC R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
 3) PLEASE SHOW THE ROOF SLOPE AT THE TILE ROOF AREA FBC
 R905.3.2
 4) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE ROOFING TILE - PLEASE
 CIRCLE THE TILE ATTACHMENT TO BE USED IN THE PRODUCT
 APPROVAL - IF USING ADHESIVE PLEASE PROVIDE THE PRODUCT
 APPROVAL FOR THE ADHESIVE.
  