Plan Review Notes
Plan Review Notes For Permit 20101383
Permit Number 20101383
Review Stop P
Sequence Number 1
Notes
Date Text
2020-11-12 15:23:4711/12/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. DOCUMENTATION SUBMITTED IN NOT DEVICE THAT IS
 LEAD-FREE WHICH SHOULD CONTAIN NOT MORE THAN
 0.25-PERCENT LEAD.
  
 2. THE THIS AUTO-FILL PVB ALSO REQUIRES TO HAVE A
 REDUCED PRESSURE ZONE VACUUM BREAKER AT THE METER WHICH
 IT UNIT HAS TO BE CERTIFIED BY THE CITY OF WEST PALM
 BEACH UNDER THE CROSS CONNECTION PROGRAM AS THIS IS A
 CONTAINMENT BACKFLOW DEVICE. THE PVB IS AN ISOLATION
 DEVICE THAT CAN BE CERTIFIED BY THE PLUMBING CONTRACTOR
 BEFORE A FINAL INSPECTION. PLEASE SUBMIT A DOCUMATATION
 FOR THE DEVICE THAT SHOWS MANUFACTURER?S SPECIFICATIONS
 FOR THE BACKFLOW PREVENTERS. THE MAKE, MODEL, AND SIZE
 OF THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE
 WORK SECTION ON THE PERMIT APPLICATION. THESE DEVICES
 REQUIRE A DOCUMENT THAT NEEDS TO SHOW THE DEVICE IS
 LEAD-FREE WHICH CONTAINS NOT MORE THAN 0.25-PERCENT
 LEAD AND APPROVED DEVICES LISTED AND PUBLISHED BY THE
 UNIVERSITY OF SOUTHERN CALIFORNIA (USC).
  
 3. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND
 FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING
 OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL
 HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR
 LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF
 DRINKING WATER PIPE AND FITTINGS.
  
 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved