2020-12-01 08:09:10 | SFR REMODEL AND ADDITION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW THE SMOKE AND CARBON MONOXIDE DETECTOR |
| LOCATIONS THROUGHOUT THE HOUSE PER FBC R314.2.2 |
| ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. AND FBC R315.1 |
| CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. |
| 2) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO |
| COMPLY WITH FBC R807.1 |
| 3) PRODUCT APPROVALS PROVIDED FOR THE WINDOWS AND DOORS |
| = THE PRODUCT APPROVAL NUMBERS DO NOT MATCH THE NUMBERS |
| SHOWN ON THE DRAWINGS WINDOW AND DOOR SCHEDULES -PLEASE |
| REVISE THE DRAWINGS OR PROVIDE THE PRODUCT APPROVALS |
| SHOWN ON THE DRAWINGS. |
| |