Plan Review Notes For Permit 20101304 |
Permit Number |
20101304 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-29 09:27:50 | 10/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE SUPPLY THE MANUFACTURER?S SPECIFICATIONS FOR | | THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF | | THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE | | WORK SECTION ON THE PERMIT APPLICATION. | | | | 2. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE | | WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD. | | | | 3. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND | | FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING | | OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL | | HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR | | LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF | | DRINKING WATER PIPE AND FITTINGS. | | | | 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS | | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY | | OF SOUTHERN CALIFORNIA (USC). | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|