2021-03-22 12:06:59COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 3RD REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) EXTERIOR COOLER IS SUBJECT TO WIND LOADS- PROVIDE
 SIGNED AND SEALED DRAWINGS FROM AN ARCHITECT OR
 ENGINEER FOR THE COOLER, COOLER FOUNDATION AND COOLER
 TIEDOWNS OR PROVIDE A MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL. FBC 1609
 2) DRAWINGS NEED TO SHOW THE WIND DESIGN DATA USED FOR
 DESIGN FBC 1603.1.4
 3) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS
 BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE
 2017 FBC.
 4) SEE NOTE NUMBER 5 ON THE PROVIDED PRODUCT APPROVAL.