Plan Review Notes
Plan Review Notes For Permit 20101267
Permit Number 20101267
Review Stop B
Sequence Number 2
Notes
Date Text
2020-12-07 13:07:30COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEED MORE INFORMATION FOR A COMPLETE REVIEW -
 OUTSIDE COOLER = NEED A SITE PLAN/SURVEY SHOWING
 EASEMENTS, WATER DRAINAGE/ RETENTION ON PROPERTY,
 COOLER LOCATION AND SETBACKS FROM PROPERTY LINES AND
 EXISTING BUILDINGS. EXTERIOR COOLER IS SUBJECT TO WIND
 LOADS- PROVIDE STRUCTURAL CALCULATIONS OR SIGNED AND
 SEALED DRAWINGS FROM AN ARCHITECT OR ENGINEER FOR THE
 COOLER, COOLER FOUNDATION AND COOLER TIEDOWNS OR
 PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL.
 FBC 1609
 INSIDE COOLER = NEED A LIFE SAFETY PLAN - SHOWING
 LOCATION AND BUILDING MEANS OF EGRESS, BLDG
 CONSTRUCTION TYPE FBC CHAPTER 6, OCCUPANCY
 CLASSIFICATION FBC CHAPTER 10 ETC.
 2) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS
 BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE
 2017 FBC.