Plan Review Notes For Permit 20101267 |
Permit Number |
20101267 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-06 14:34:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | SOME OF THESE ITEMS MAY BE EXISTING BUT ARE NOT | | INDICATED, PLEASE INDICATE OR CORRECT. | | | | | | 1) I AM CONFUSED OF WHAT THE PROPOSED PROJECT IS OR | | CONSIST OF. | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK | | | | | | | | 1A) WHAT DOES SHEET 2 OF 4 INDICATE? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 1B) WHAT DOES SHEET 3 OF 4 INDICATE? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 1C) PLEASE PROVIDE A DETAILED SITE PLAN THAT MAY ASSIST | | WITH THE ABOVE QUESTIONS. | | | | | | | | 2) SHEET 2 OF 4 APPEARS TO INDICATE A NEW DOOR. IS THIS | | CORRECT? | | | | PLEASE PROVIDE THE DOOR HANDLE INFO SHOWING THAT A | | PERSON CAN'T BE LOCKED INSIDE. | | | | | | | | 3) THERE IS NO INDICATION OF AN EXIT SIGN IF # 2 | | CREATES A NEW ROOM. | | | | PLEASE PROVIDE DETAILS. | | | | | | 4) THERE IS NOT INCIATION OF LIGHTING OR EMERGENCY | | LIGHTING SHOULD THE ROOM GO DARK. | | | | THE EXIT SIGN OF AN EMERGENCY LIGHT MAY NEED TO BE | | INSTALLED IF NOT CONNECTED TO EMERGENCY POWER. | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | | | | | |
|