Plan Review Notes
Plan Review Notes For Permit 20101251
Permit Number 20101251
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-11-04 13:13:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE EXISTING FIRE RATED WALLS THAT ARE BEING
 REPLACED, HOWEVER, THERE ARE NO INDICATIONS OF A LISTED
 RATED WALL CALL-OUT TO ENSURE PROPER CONSTRUCTION.
  
 PER NFPA 1 CH 8
  
 8.3.1.3 WALLS USED AS FIRE BARRIERS SHALL COMPLY WITH
 CHAPTER 7 OF
 NFPA 221, STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE
 WALLS, AND
 FIRE BARRIER WALLS. THE NFPA 221 LIMITATION ON
 PERCENTAGE WIDTH OF
 OPENINGS SHALL NOT APPLY.
  
 8.3.2 WALLS.
 8.3.2.1 THE FIRE-RESISTIVE MATERIALS, ASSEMBLIES, AND
 SYSTEMS USED SHALL
 BE LIMITED TO THOSE PERMITTED IN THIS CODE AND THIS
 CHAPTER.
  
 8.3.2.2 THE CONSTRUCTION MATERIALS AND DETAILS FOR
 FIRE-RESISTIVE
 ASSEMBLIES AND SYSTEMS FOR WALLS DESCRIBED SHALL COMPLY
 WITH ALL
 OTHER PROVISIONS OF THIS CODE, EXCEPT AS MODIFIED
 HEREIN.
  
 NFPA 221
  
 4.3 FIRE RESISTANCE RATINGS
 4.3.1 THE FIRE RESISTANCE RATING OF ASSEMBLIES SHALL BE
 DETERMINED
 IN ACCORDANCE, ASTM E 119, STANDARD TEST METHODS FOR
 FIRE
 TESTS OF BUILDING CONSTRUCTION AND MATERIALS, OR
 ANSI/UL 263, STANDARD
 FOR FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS,
 OR OTHER
 APPROVED TEST METHODS OR ANALYTICAL METHODS IN
 ACCORDANCE WITH
 4.3.2.
  
 PLEASE PROVIDE A DETAILED LISTED FIRE RATED WALL
 CALL-OUT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  