2020-11-04 10:39:441ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20101221
 11/4/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER DOES NOT INCLUDE THE 40,000 BTUH RANGE
 INSTALLED UNDER PERMIT 13020524. PLEASE REVISE THE
 RISER, AND ADD THE GAS LOAD TO THE TOTAL LOAD SHOWN ON
 THE DRAWING- SECTIONS G2412.3, G2412.4, G2412.3, &
 G2412.4 FBC RES.
  
 2) THE SPECS FOR THE GENERATOR SUBMITTED UNDER PERMIT-
 20071265 INDICATE A FULL LOAD CAPACITY OF 306,000 BTUH
 AND A GAS INPUT PRESSURE OF 3.5- 7 IN. W.C. PLEASE
 CORRECT THE RISER AND LOAD TOTAL, AND SUBMIT SPECS FOR
 THE NEW REGULATORS MARKED-UP OR HIGHLIGHTED TO SHOW THE
 SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND
 PRESSURES, SPRING DATA, AND ORIFICE SIZE- SECTION
 G2421.1 FBC RES.
  
 3) LIST THE PIPE SIZING TABLES ON THE DRAWING- SECTION
 G2413.3 & G2413.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  